Installation Place - Toshiba RAS-24N3KCV1 Installation Manual

Split type
Table of Contents

Advertisement

Installation Place

• A place which provides enough spaces around the outdoor unit as shown
in the diagram.
• A place which can bear the weight of the outdoor unit and does not allow
an increase in noise level and vibration.
• A place where the operation noise and discharged air do not disturb your
neighbors.
• A place which is not exposed to a strong wind.
• A place free of a leakage of combustible gases.
• A place which does not block a passage.
• When the outdoor unit is to be installed in an elevated position, be sure to
secure its feet.
• An allowable length of the connecting pipe is up to 30 m.
• There is no need to add refrigerant as long as the length of the connection
piping is 20 m or less.
• You will need to add 30g of refrigerant per meter of added connection
piping for installations requiring connection piping to be between 21 m to
30 m.
• An allowable height level is up to 20 m.
• A place where the drain water does not cause any problems.
CAUTION
1. Install the outdoor unit in a location where the discharge air is not
blocked.
2. When an outdoor unit is installed in a location that is always exposed
to strong winds like a coast or on the high stories of a building, secure
normal fan operation by using a duct or wind shield.
3. When installing the outdoor unit in a location that is constantly
exposed to strong winds such as on the upper stairs or rooftop of a
building, apply the windproofi ng measures referred to in the following
examples.
1) Install the unit so that its discharge port faces the wall of the
building.
Keep a distance 500 mm or more between the unit and wall
surface.
2) Consider the wind direction during the operational season of the air
conditioner, and install the unit so that the discharge port is set at a
right angle relative to the wind direction.
Strong wind
• When using an air conditioner under low outside temperature
conditions (Outside temp:-5 °C or lower) in COOL mode, prepare
a duct or wind shield so that it is not affected by the wind.
<Example>
Wind shield
500 mm
Strong wind
Wind shield
• As shown in the fi gure below, install the foundation and vibration-proof
rubber pads to directly support the bottom surface of the fi xing leg that is
in contact with and underneath the bottom plate of the outdoor unit.
* When installing the foundation for an outdoor unit with downward piping,
consider the piping work.
Fixing leg
Foundation
Foundation
Support the bottom surface of the fi xing leg that is in contact
with and underneath the bottom plate of the outdoor unit.
If only the end of the
fi xing leg is supported,
it may deform.
Foundation
Set the out margin of the anchor bolt to 15 mm or less.
• When water is to be drained through the drain hose, attach the following
drain nipple and waterproof rubber cap, and use the drain hose (Inner
dia.: 16 mm) sold on the market. Also seal the screws securely with
silicone material, etc., to prevent water from leaking.
Some conditions may cause dewing or dripping of water.
• When collectively draining discharged water completely, use a drain pan.
8
GOOD
Absorb vibration
with vibration-proof
rubber pads
GOOD
Bottom plate of
outdoor unit
NO GOOD
Do not support the
outdoor unit only with
the fi xing leg.
15 or less