Malfunction Of Transmission Between Outdoor Units; U7" Malfunction Of Transmission Between Outdoor Units - Daikin VRV II REYQ8MY1B Service Manual

R410a heat recovery 50hz
Table of Contents

Advertisement

Si39-306
2.48 " U7 "

Malfunction of Transmission between Outdoor Units

U7
Remote
Controller
Display
Applicable
All models of indoor units
Models
Method of
Microcomputer checks if transmission between indoor unit and remote controller is normal.
Malfunction
Detection
Malfunction
When transmission is not carried out normally for a certain amount of time
Decision
Conditions
Supposed
Causes
Troubleshooting
Improper connection of transmission wiring between outdoor unit and outdoor unit outside
control adaptor
Improper cool/heat selection
Improper cool/heat unified address (outdoor unit, external control adaptor for outdoor unit)
Defect of outdoor unit PC board (A1P)
Defect of outdoor unit outside control adaptor
Improper connection of transmission wiring between outdoor units of multi outdoor unit
connection.
Troubleshooting by Indication on the Remote Controller
203

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents