Stopping Operation - Daikin VRV II REYQ8MY1B Service Manual

R410a heat recovery 50hz
Table of Contents

Advertisement

Si39-306
3.7

Stopping Operation

This operation is used to define the operation of the actuator while the system stops.
3.7.1 When System is in Stop Mode
Compressor
Outdoor unit fan
Four way valve 1
Four way valve 2
Main motorized valve (EV1)
Sub motorized valve (EV2)
Sub-cooling motorized valve (EV3)
Hot gas bypass valve (SVP)
Oil equalization valve (SVO)
Receiver gas charging valve (SVL)
Receiver gas discharge valve (SVG)
Discharge pipe stop valve (SVR)
Non-operating unit liquid pipe stop valve (SVSL)
High pressure gas pipe pressure reduction valve (SVC)
Ending conditions
* Actuators are based on REYQ16M.
Function
Actuator
Operation
OFF
OFF
Holds ON
Holds ON
0 pls
0 pls
0 pls
OFF
OFF
OFF
OFF
Holds ON
ON
Holds ON
Indoor unit thermostat turned ON.
Special Control