Refrigerant Flow Diagram - Sanyo SAP-K92A Technical & Service Manual

Multi-split system
Hide thumbs Also See for SAP-K92A:
Table of Contents

Advertisement

6. REFRIGERANT FLOW DIAGRAM

SAP – K92A ( × 2)
Indoor Unit
Outdoor Unit
SAP – CM1822A
Indoor Unit A
Indoor Unit B
Insulation of Refrigerant Tubing
IMPORTANT
Because capillary tubing is used in the outdoor unit, both the
wide and narrow tubes of this air conditioner become cold. To
prevent heat loss and wet floors due to dripping of condensa-
tion, both tubes must be well insulated with a proper insula-
tion material. The thickness of the insulation should be a min.
8 mm.
CAUTION
Wide tube
O.D.
ø9.52mm
(3/8 ")
Narrow tube
O.D.
ø6.35 mm
(1/4")
After a tube has been insulated,
never try to bend it into a narrow
curve because it can cause the tube
to break or crack.
Outdoor Unit
A
B
Accumulator
Wide tube
service
valve
Narrow tube
service
valve
B
Capillary tube
A
Thickness:
Min. 8 mm
Wide tube
11
Accumulator
Insulation
Thickness:
Min. 8 mm
Narrow tube

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sap-cm1822a

Table of Contents