Mitsubishi Electric par-u02meda Installation Manual page 6

City multi control system smart me controller
Hide thumbs Also See for par-u02meda:

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1
4
System diagram
Outdoor unit
051
TB7
TB3
Outdoor unit
056
TB7
TB3
000
CENTRALIZED CONTROLLER AG-150A
Centralized
Power supply
controller
unit
*1 The power consumption coefticient of the Smart ME Controller is "0.5" and that of a ME Remote Controller
(PAR-F27MEA) is "0.25".
If the number of Smart ME Controllers is high and the total power supply they require exceeds the outdoor unit's
ability to supply power, a Transmission booster (PAC-SF46EPA) will be required.
Outdoor unit
32
(1) Wiring from the remote controller
• Connect to TB5 (terminal block for indoor-outdoor transmission cable) on any indoor unit in same
M-NET system.
• The terminal block has no polarity. Connect to the terminals M1 and M2.
(2) Operating in a group (Groups 01, 02, 03, and 04)
• Assign the lowest address to the main indoor unit in the group.
The remote controller address should be set to a number that equals the main indoor unit address
plus 100.
(3) Up to two remote controllers (main and sub) can be connected to an indoor unit or a group of
indoor units.
• Connect the main and sub remote controllers in the same way as described in (1) above.
• Be sure to set the main and sub remote controller addresses.
The sub remote controller address should be set to a number that equals the main indoor unit
address plus 150.
- Remote controllers cannot be wired together. Only one
CAUTION
- The ME remote controller and MA remote controller
Group 01
Group 02
Indoor unit
Indoor unit
001
002
TB5
TB5
101
102
Smart ME
Smart ME
Controller *1
Controller
Group 04
Indoor unit
Indoor unit
009
TB5
TB5
107
157
Smart ME
Smart ME
Controller
Controller
Transmission booster
25
cable can be connected to the remote controller terminal
block.
cannot be connected in the same group.
Group 03
Indoor unit
Indoor unit
003
TB5
TB5
Smart ME
Controller
Indoor unit
Indoor unit
008
007
TB5
TB5
Indoor unit
(*1)
1
*1: "7" for the P200 and P250 models
– 5 –
LOSSNAY unit
005
004
104
Advanced HVAC
CONTROLLER (AHC)
006
201
Smart ME Controller
0.5
Main
remote
controller
Sub
remote
controller