2-4. Outer Dimensions of Outdoor Unit
608
A
Diagram of Outdoor Unit Installation
2-5.
Never install only a single indoor unit.
Be sure to connect indoor and outdoor units only in
combinations that are listed in the catalog or in the
combination table that was provided with the outdoor unit.
(Use caution. Connecting any other model may result in
operation failure and malfunction.)
The dimensions indicated by
spaces that are required in order to maintain
performance. Install in a location where the dimensions
indicated by
of the unit are unobstructed. In principle, the top direction
should be unobstructed.
Ensure 15cm
of space if a
drain hose is to
be used.
Base (not provided)
(concrete or similar material)
85
in the figure below are
are ensured, and where 2 or more faces
B
A
Fasten with anchor bolts
(not provided)
(3/8" or M10, 4 locations)
A
790
70
Fig. 6a
Power breaker
Service space
Ground
wire
(not
provided)
Fig. 6b
7
Service valve on
narrow tube side
(Outer diameter ø 6.35 )
Service valve on
wide tube side
(Outer diameter ø 9.52 )
46
142
unit: mm
Indoor unit B
Indoor unit A
Access panel C