Emerson XR75CX Installation And Operation Manual page 18

Digital controller for medium-low temperature refrigeration applications
Table of Contents

Advertisement

Code
Parameter
AC2
Compressor OFF with high
temperature alarm of condenser
tbA
Alarm relay silencing (with
oA3=ALr)
oA3
Fourth relay configuration (1-4)
AOP
Alarm relay polarity
i1P
Digital input polarity (18-20)
i1F
Digital input configuration (18-
20)
i2P
2nd digital input polarity (18-
19)
i2F
2nd digital input configuration
(18-19)
did
(0 to 255 min) with i2F= EAL
or i2F = bAL digital input
alarm delay (18-20)
doA
Door open signaling delay
nPS
Pressure switch number
Odc
Compressor status when open
door
rrd
Outputs restart after doA alarm
HES
Temperature increase during
the Energy Saving cycle
TO SET CURRENT TIME AND WEEKLY HOLIDAYS (ONLY FOR MODELS WITH RTC)
Hur
Current hour (0 to 23 hr)
Min
Current minute (0 to 59 min)
dAY
Current day (Sun to SAt)
Hd1
First weekly holiday (Sun to
not used)
Table 7-1 - List of Parameters
12 • XR75CX I&O Manual
n = no: compressor keeps on working
Y = yes, compressor is switched OFF until the alarm is present, in any case regulation
restarts after Ac time at minimum.
AUXILIARY RELAY
n= silencing disabled: alarm relay stays ON until alarm condition lasts
y =silencing enabled: alarm relay is switched OFF by pressing a key during an alarm
dEF, FAn: do not select it! ALr: alarm; Lig: light; AUS: Auxiliary relay; onF: always
ON with device ON; db= neutral zone; cP2 = do not select it!; dEF2: do not select it!;
HES: night blind
Set if the alarm relay is open or closed when an alarm happens.
CL= terminals 1-4 closed during an alarm
oP = terminals 1-4 open during an alarm
DIGITAL INPUTS
oP = the digital input is activated by opening the contact
CL = the digital input is activated by closing the contact
dor = door switch function
dEF = activation of a defrost cycle
oP = the digital input is activated by opening the contact
CL = the digital input is activated by closing the contact
EAL= external alarm: "EA" message is displayed
bAL= serious alarm "CA" message is displayed
PAL= pressure switch alarm, "CA" message is displayed
dor = door switch function
dEF= activation of a defrost cycle
ES = energy saving
AUS = auxiliary relay activation with oA3 = AUS
Htr = kind of action inversion (cooling – heating)
FAn = fan
HdF = Holiday defrost (enable only with RTC)
onF = to switch the controller OFF
Delay between the detection of the external alarm condition and its signaling. When i2F
= PAL: time for pressure switch function: time interval to calculate the number of the
pressure switch activation.
(0 to 255 min)
(0 to 15)
Number of activation of the pressure switch, during the did interval, before signaling
the alarm event (i2F = PAL). If the nPS activation in the did time is reached, switch
OFF and ON the device to restart normal regulation.
no = normal
Fan = fan OFF
CPr = compressor OFF
F_C = compressor and fan OFF
no = outputs not affected by the doA alarm
yES = outputs restart with the doA alarm
(-30.0°C to 30.0°C)
Sets the increasing value of the setpoint during the Energy Saving cycle.
Sets the current hour.
Sets the current minute.
Sets the current day of the week.
Set the first day of the week that follows the holiday times.
Function