6.4 Ambient Temperature

The maximum ambient temperature for the operator panel is provided in the
specifications. The ambient temperature refers to the temperature in the device
cabinet which cools the panel's electronics.
Top
50
Operator
panel
°
30
C outside
Middle
45
Bottom
40
In most cases, the ambient temperature for the operator panel is significantly higher
than the device cabinet's ambient temperature.
If the cabinet is tall and there are a number of heat-generating devices, the
temperature at the top of the cabinet will be considerably higher than the theoretical
temperature increase that would be expected. All electronics are sensitive to heat. The
lifespan of an electrolytic capacitor is cut in half with an 8-10 ° increase in
temperature. A 15-20 ° temperature increase results in a quarter of the lifespan etc.
Rittal has a good program for estimating the anticipated average temperature in the
cabinet as well as a large program for controlling the temperature in the device
cabinet.
An enamel-coated steel cabinet has a radiant heat value of 5.5 W/m
Installing a fan inside the cabinet will even out the temperature, while moving air
provides considerably better cooling than still air. A suitable fan is a 120 x 120 mm
axial fan, available in 24 V DC, 115 and 230 V AC.
Install the fan so that it sits in the cooler area and will blow cold air against the
operator panel. If the fan is mounted at the top and sucks air upwards, the fan's
ambient temperature will be higher = shorter lifespan.
A good fan with a ball-bearing mounting has an expected lifespan of at least 40,000
hours (not a guaranteed lifespan) at 40 °C. This corresponds to at least 4 years of
continuous use. If a thermostat is installed, the fan only needs to come on when
needed.
Large graphic terminals draw only one fifth of the current when the background
lighting is off. The loss effect drops from e.g. 25 W to only 5 W.
The operator panel's loss effect = supply voltage x current. Virtually no power goes
to external users and no loss effects due to inputs.
24
°
inside
Power
Power
°
inside
Power
°
inside
Axial fan
120x120 mm
Airflow
5354
2
and degrees C.
Mitsubishi Electric, MA00776C