Chilled/hot water piping

Chilled/Hot Water Exchanger water connections are
grooved. Thoroughly flush all water piping to the unit
before making the final piping connections to the unit.
Components and layout will vary slightly, depending on
the location of connections and the water sources.
FWD
Power supply
CAUTION Equipment Damage! If using an acidic
Capacities
commercial flushing solution, construct a temporary
Cooling capacity on water (1)
Heating capacity on water (2)
bypass around the unit to prevent damage to internal
Fan motor
components of chilled/hot water exchanger.
Fan power input (3)
Current amps (3)
CAUTION Proper Water Treatment! The use of untreated
Start-up amps
or improperly treated water in the unit may result
Air flow
minimum
in scaling, erosion, corrosion, algae or slime. It is
nominal
recommended that the service of a qualified water
maximum
treatment specialist be engaged to determine what
Main coil
water treatment, if any, is required. Trane assumes
Water entering/leaving connections
no responsibility for equipment failures which results
Electric heater (accessory for blower only)
from untreated or improperly treated water or saline or
Electric power supply
brackish water.
Heating capacity
Hot water coil (accessory for blower only)
Drainage
Heating capacity (4)
G2 filter (filter box accessory)
Locate the unit near a large capacity drain for water
Quantity
vessel draining down during shutdown or repair.
Dimensions ( LxWxth)
G4 filter (filter box accessory)
Chilled/hot water exchangers are provided with drain
Quantity
connections. Refer to "Water Piping. " All local and
Dimensions ( LxWxth)
national codes apply.
Condensate pump (accessory)
Water flow - lift height
Water Treatment
Not available for FWD30 and FWD45
Sound level (L/M/H speed)
In the Chilled/Hot Water Exchanger the following material
Sound pressure level (5)
Sound power level (5)
are in contact with water:
Unit dimensions
Plate material: AISI 316 EN 10028-7 - 1.4401 +2B/2R

Width x Depth

Height
Connection: AISI 316 EN 10272
Shipped unit dimensions
-1.4401/1.4404/1.4435/1.4436 - 1E
Width x Depth
Height
Braze alloy: EN-13388, ISO Copper CU-HCP
Weight
Colour
When the unit is supplied with hydraulic module, the
Recommended fuse size
following additional materials are in contact with water:
Unit alone (aM/gI)
Unit with electric heater (gI)
Pump frame and connections are made of cast iron
Water pipes are made of carbon steel
(1) Conditions: Water entering/leaving temperature: 7/12 °C, Air inlet temperature 27/19°C DB/WB - Nominal air flow
(2) Conditions: Water entering/leaving temperature: 50/45 °C, Air inlet temperature 20°C DB - Nominal air flow
Pipe sealings are made of EPDM rubber (ethylene
(3) At high speed with nominal air flow.
(4) Water entering/leaving temperature 90/70 °C, air inlet temperature 20 °C DB, Nominal air flow.
propylene diene monomer rubber)
(5) A rectangular glass wool duct 1m50 long is placed on the blower.The measurement is taken in the room containing the blower unit.
Pump sealings are made of silicon carbide
Heat exchanger operating limits:
FWD:
Strainer is made of stainless steel
*water temperature: max 100° C
Dirt, scale, products of corrosion, and other foreign
*absolute service pressure: min 1 bar/max 11 bars
material will adversely affect heat transfer between the
Accessories - Hot water coil:
water and system components. Foreign matter in the
*water temperature: min. +2° C/max. 100° C
*absolute service pressure: min 1 bar/max 11 bars
chilled-water system can also increase pressure drop and
consequently, reduce water flow. Proper water treatment
must be determined locally, depending on the type of
system and local water characteristics.
Neither salt nor brackish water is recommended for
use in Trane air-cooled unit. Use of either will lead to an
unpredictably shorter life cycle. Trane encourages the
employment of a reputable water treatment specialist,
familiar with local water conditions, to assist in this
determination and in the establishment of a proper water
treatment program.
30
4
Technical Data
If calcium chloride is used for water treatment, an
applicable corrosion inhibitor must also be used. Failure
to do so may result in damage to system components.
Do not use untreated or improperly treated water.
Equipment damage may occur.
08
(V/Ph/Hz)
Piping
(kW)
5,2
(kW)
6,3
Piping components include all devices and controls
(type)
used to provide proper water system operation and unit
(kW)
0,23
operating safety. A typical Chilled/Hot Water Exchanger
(A)
1,1
piping is shown below.
(A)
3,2
Figure 5 - Unit typical water circuit
(m
/h)
490
3
(m
/h)
820
3
(m
/h)
980
3
(type)
(Dia)
3/4"
(V/Ph/Hz)
230/1/50
(kW)
2/4
(kW)
6,3
2
(mm)
386x221x8
-
(mm)
-
(type)
(l/h - mm)
1 = Pressure gauges: show entering and leaving water
(dB(A))
36/40/43
pressure
(dB(A))
46/50/53
2 = Balancing valve: adjusts water flow.
(mm)
890 x 600
3 = Air purge allows to remove the air from the water
(mm)
250
circuit during fill up.
(mm)
933 x 644
4 = Stop valves: isolate the unit and water circuiting
(mm)
260
pump during maintenance operations.
(kg)
32
5 = Thermometers: indicate chilled water entering and
leaving temperatures.
(A)
8/16
(A)
16 (2kW),25 (4kW)
6 = Expansion compensators: avoid mechanical stress
between the unit and piping installation.
7 = Stop valve located on the outlet connection: used to
measure the water pressure inlet or outlet of chilled/hot
water exchanger.
8 = Strainer: avoid to get heat exchangers dirty. All
installation must be equipped with efficient strainer in
order that only clean water enters into exchanger. If
there is no strainer, reserve will be formulated by the
Trane technician at the start-up of the unit. The trainer
used must be able to stop all particles with a diameter
greater than 1 mm.
9 = Draining: used as the draining the plate heat
exchanger.
10 = Do not start the unit with low water volume or not
enough pressurized circuit.
Note: A pressure switch device to detect lack of water
is not included in the pump package. Installation of this
type of device is highly recommended to avoid sealing
damage due to operation of pump without enough
water.
12
20
230/1/50
8,3
15
11,9
18,9
2 x direct drive centrifugal
0,46
0,65
2,2
3,1
5,5
9,3
980
1400
1650
2300
1970
2600
ISO R7 rotating female
3/4"
1 1/2"
230/1/50 or 400/3/50
400/3/50
8
10
12
17,4
2
2
486x271x8
586x321x8
2
2
486x264x48
586x314x48
Centrifugal
24 - 500
38/41/44
46/50/53
48/51/54
56/60/63
1090 x 710
1290 x 820
300
350
1133 x 754
1333 x 864
310
360
46
61
galvanised steel
8/16
8/16
40 (230V),3*16 (400V)
3*20
30
45
18,8
30,1
20,9
38,2
1,04
1,51
4,7
5,5
14,1
16,5
1800
2700
3000
4500
3600
5400
1 1/2"
1 1/2"
400/3/50
400/3/50
12
12
22,4
34,5
2
2
586*421*8
586*621*8
2
2
586*414*48
586*614*48
47/52/57
47/52/58
57/62/67
57/62/68
1290 x 970
1290 x 1090
450
650
1333 x 1008
1333*1133
460
660
76
118
8/25
8/25
3*25
3*25
CG-SVX051A-GB
UNT-PRC002-GB