Display and Operation

Mode
Display of operation
mode
Indicators
1 Remote
temperature sensor
Up :
Increase setpoint
(Parameter setting:
scroll menu options
and parameters)
Left (POWER):
Press < 2 sec.: Toggle Economy -
Comfort mode or switch from OFF
to ON
Press > 2 sec.: Turn unit OFF. Text
OFF displayed with current time
(deluxe) temperature (standard)
(Parameter setting: Return to
previous level. ESC)
Comfort (occupied)
Economy (unoccupied):
OFF
Energy Hold Off
Heating
Cooling
Fan
Manual mode
Schedule
Power Failure
All the parameters and set points are memorized and do not need to be reentered. Depending on UP05 the unit will
remain switched off, switch on automatically or return to the operation mode it was in before the power failure.
Deluxe version only: Timer operation and daytime setting will be retained for 24h. The controller has to be connected
to a power supply for at least 10 hours for the backup function to operate accordingly.
Frost Protection
The controller will enter frost protection mode if the room temperature drops below 5°C (41°F). All heating outputs will
be fully opened. Frost protection mode will be left once the temperature reaches 10°C (50°F). Frost protection display
will remain until a button is pressed. Frost protection can be enabled/disabled using user parameter UP-09
Error messages
Following error condition may be shown:
Err1:
The connection to the temperature sensor may be interrupted or the temperature sensor is damaged.
The output is switched off. Verify parameter settings and wiring.
FP:
Steady: Frost protection is active.
Blinking: Frost protection activated in the past and is now inactive. Confirm with OPTION key.
Doc: 70-00-0181, V3.0 Date: 20120424
Subject to alteration
Operation mode
All control functions operating per set points.
Set points shifted according to Parameters FC04.
Economy mode and setpoint shift may be disabled with UP06
Outputs are off, inputs monitored for alarm condition
Output activates if temperature lower than setpoint
Output activates if temperature higher than setpoint
Fan is running, the vertical bars show active speed 1-3
Manual override of fan speed, fan only mode or override of time schedule active.
Deluxe only: Time schedule is active
© Vector Controls GmbH, Switzerland
TLC3-FCR-M Engineering Manual
Large Digits
Display of input or parameter value.
Small Digits
Display of setpoint, clock or
parameter number.
Vertical Bar
(fan speeds 1-3 or proportional
output in 10% steps)
Right (OPTION)
Press < 2 sec.: Select fan speed:
Low, medium, high or auto
Press > 2 sec.: Manual H/C change
(Parameter setting: ENTER to
select menu option, accept
parameter change)
Down:
Decrease setpoint
(Parameter setting: scroll menu
options and parameters)
Page 4