TLC3-FCR-M-U
Programmable PID Fan Coil controller
Features
Proven PID controls algorithm reduces room temperature fluctuations
and energy consumption
Low power energy consumption: < 1W per unit
Temperature control for 2- and 4-pipe fan coil systems.
Automatic fan control for three stage fans.
Cost saving option with Economy functionality and set point limitations
Control for modulating heating, cooling and fan only operation modes
Password protected programmable user and control parameters
Setpoint range limitation
o
Access control for setpoints, fan speeds and mode change
o
Access control for heat/cool change and time programs
o
Select your display contents
o
Selectable behavior after return from power failure
o
Temperature display in Celsius or Fahrenheit
Deluxe Version:
Clock and time schedule functions with power failure protection
Blue backlight for LCD
Infrared remote controller option:
With special features for Boost and delayed switching on or off
Applications
Air Only Systems:
Constant or Variable Air Volume systems with three stage fans for single or dual duct systems
o
Air/Water Systems:
Fan Coil units for 2-pipe or 4-pipe systems
o
radiator control, chilled ceiling
o
Simple individual room control for hotel rooms, meeting rooms, etc.
PID-Control of up to 2 modulating valves for heating and cooling

General Description

The TLC3-FCR-M-U is a stand-alone electronic fan coil controller with one control loop. The TLC3-FCR-M2-U is designed
for 2-pipe modulating fan coil systems and features 1 NTC temperature sensor input, one external passive input for
temperature or open contact, three binary outputs (Relays) and one analog output (0-10VDC).
The TLC3-FCR-M4-U is designed for 4-pipe modulating fan coil systems and features 1 NTC temperature sensor input,
three binary outputs (Relays) and two analog outputs (0-10VDC) for heating and cooling.
A detailed parameterization is possible with the use of a simple configuration routine. The TLC3-FCR-M-U can be
configured using the standard operation terminal. No special tools or software is required.
Ordering
Item Name
Item code
TLC3-FCR-M2-U-24
40-10 0141
TLC3-FCR-M2-U-120
40-10 0151
TLC3-FCR-M2-U-230
40-10 0102
TLC3-FCR-M2-U-D-24
40-10 0146
TLC3-FCR-M2-U-D-120 40-10 0156
TLC3-FCR-M2-U-D-230 40-10 0103
TLC3-FCR-M4-U-24
40-10 0142
TLC3-FCR-M4-U-120
40-10 0152
TLC3-FCR-M4-U-230
40-10 0106
TLC3-FCR-M4-U-D-24
40-10 0147
TLC3-FCR-M4-U-D-120 40-10 0157
TLC3-FCR-M4-U-D-230 40-10 0107
-1
-W01
Selection of fans
Do not directly connect devices that exceed 2A. Observe startup current on inductive loads! Do not connect more than
one fan coil unit to one controller.
Modulating Actuators:
Choose actuators with an input signal type of 0-10V DC or 2-10V DC. Observe maximal signal current of 1mA!
Doc: 70-00-0182, V3.0 Date: 20120424
Subject to alteration
TLC3-FCR-M-U Engineering Manual
Variant
Power
24VAC/DC
Standard
120VAC
230VAC
24VAC/DC
Deluxe
120VAC
230VAC
24VAC/DC
Standard
120VAC
230VAC
24VAC/DC
Deluxe
120VAC
230VAC
Cooling only
© Vector Controls GmbH, Switzerland
Features
Fan coil controller with:
1 TI int, 1 external input
3 DO (Relay) Fan control
1 AO (0-10VDC) PID valve control
1 TI int
3 DO (Relay) Fan control
2 AO (0-10VDC) PID valve control
Add to name or code for special settings
Page 1

Advertisement

Table of Contents
loading

Summary of Contents for Vector TLC3-FCR-M-U

  • Page 1: General Description

    PID-Control of up to 2 modulating valves for heating and cooling General Description The TLC3-FCR-M-U is a stand-alone electronic fan coil controller with one control loop. The TLC3-FCR-M2-U is designed for 2-pipe modulating fan coil systems and features 1 NTC temperature sensor input, one external passive input for temperature or open contact, three binary outputs (Relays) and one analog output (0-10VDC).
  • Page 2: Technical Specification

    60 x 50 x 32mm (2.4 x 2.0 x 1.3 in.) Distance for mounting screws: Horizontal 55 to 60mm (2.2 to 2.4 in.) Vertical: 55 to 93mm (2.2 to 3.7 in.) Doc: 70-00-0182, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 2 Subject to alteration...
  • Page 3: Mounting Location

    0…10 V DC TLC3-FCR-M4-U: Signal common: Common 0 potential for inputs and analog outputs. Analog cooling output: 0…10 V DC Analog heating output: 0…10 V DC Doc: 70-00-0182, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 3 Subject to alteration...
  • Page 4: Display And Operation

    The output is switched off. Verify parameter settings and wiring. Steady: Frost protection is active. Blinking: Frost protection activated in the past and is now inactive. Confirm with OPTION key. Doc: 70-00-0182, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 4 Subject to alteration...
  • Page 5: Clock Operation

    A blinking clock indicates that the time needs to be set. Time programs will not operate if the time is not defined.  See chapter operation, advanced settings for instructions on how to set the time. Access to time schedules may be disabled with UP-04  Doc: 70-00-0182, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 5 Subject to alteration...
  • Page 6: Clock Settings

    Repeatedly pressing the mode button may activate the following operation modes: HEAT, COOL and FAN ONLY. The mode change may be disabled using the UP parameters. Note: The remote controller is currently only available in °C mode. Doc: 70-00-0182, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 6 Subject to alteration...
  • Page 7: User Parameters

    Setting of user parameters The TLC3-FCR-M-U is an intelligent controller and can be adapted to fit perfectly into your fan coil application. The control operation is defined by parameters. The parameters are set during operation by using the standard operation terminal.
  • Page 8: Control Configuration

    Depending on the room size and heating / cooling equipment used a value between 0.1 and 1.5 should be sufficient. Below are suggested values: Heating: K : 0.1-0.5 Cooling: K : 0.3-0.8 Doc: 70-00-0182, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 8 Subject to alteration...
  • Page 9: Configuration Of Outputs

    Dry contact: Heating if contact closed FC21 > FC22 25°C (77F) 15°C (59F) Dry contact: Cooling if contact closed FC21 < FC22 15°C (59F) 25°C (77F) Doc: 70-00-0182, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 9 Subject to alteration...
  • Page 10 TLC3-FCR-M-U Engineering Manual Notes: Doc: 70-00-0182, V3.0 Date: 20120424 © Vector Controls GmbH, Switzerland Page 10 Subject to alteration...