Mounting location
 Install the controller on an easy accessible interior wall, approx. 1.5 m above the floor in an area of average
temperature.
 Avoid direct sunlight or other heat sources, e.g. the area above radiators and heat emitting equipment.
 Avoid locations behind doors, outside walls and below or above air discharge grills and diffusers.
 Location of mounting is less critical if external temperature sensors are used.
Installation
1.
Connect the wires to be connected to the terminals of the power case according to wiring diagram
2.
Install the mounting plate to the flush mounting box. Make sure that the nipple with the front holding screw is
facing to the ground. Make sure the mounting screw heads do not stand out more than 5 mm (0.2") off the
surface of the mounting plate.
3.
Slide the two latches located on the top of the front part into the hooks at the upper side of the mounting plate.
4.
Carefully lower the front part until the interconnector reaches the mounting-plate. Continue pressing in a gentle
way until the front part is fully connected. While inserting the connectors, a slight resistance can be felt. This is
normal. Do not use excessive force!
5.
With a Philips-type screw driver of size #2, carefully tighten the front holding screw to secure the front part to
the mounting plate. This screw is located on the front lower side of the unit. There is no need to tighten the
screw too much.
Wiring Diagram
230V AC
2
L
1
3
N
Y1
0V
Fan
Low
230V AC
2
L
1
3
N
Y1
0V
Fan
Low
Description:
N
Power supply:
L
Power supply:
Y1
Binary output 230V AC:
Y2
Binary output 230V AC:
Y3
Binary output 230V AC:
TLC3-FCR-M2:
M
Signal common:
X1
External input:
U1
Analog output:
TLC3-FCR-M4:
M
Signal common:
U2
Analog cooling output:
U1
Analog heating output:
Doc: 70-00-0181, V3.0 Date: 20120424
Subject to alteration
X
SGND
T EXT
IN
6
7
M
X1
4
5
Y2
Y3
Fan
Fan
Med
High
SGND
AO2
Cool
6
7
M
U2
4
5
Y2
Y3
Fan
Fan
Med
High
© Vector Controls GmbH, Switzerland
TLC3-FCR-M Engineering Manual
AO1
8
X
U1
T INT
TLC3-FCR-M2
AO1
Heat
8
X
T INT
U1
TLC3-FCR-M4
0V Neutral
230VAC
Fan speed low
Fan speed medium
Fan speed high
Common 0 potential for inputs and analog outputs.
NTC 10kΩ @ 25°C (77°F) or open contact to SGND
0...10 V DC
Common 0 potential for inputs and analog outputs.
0...10 V DC
0...10 V DC
Page 3