Technical Specification

Power Supply
Operating Voltage
AC voltage: 50/60Hz
Power Consumption
Electrical Connection
Deluxe type only: Power backup for real time clock
Signal Inputs
Temperature Inputs
Range
Accuracy
Signal Outputs
Digital Switching Outputs
Switching Type
AC Switching power
Insulation strength
between relays contacts and system electronics:
between neighboring relays contacts
Analog Outputs
Output Signal
Resolution
Minimum impedance
Environment
Operation
Climatic Conditions
Temperature
Humidity
Transport & Storage
Climatic Conditions
Temperature
Humidity
Mechanical Conditions
Standards
Product standards
Automatic electrical controls for household and similar use
Special requirement on temperature dependent controls
Electromagnetic compatibility for
domestic sector
Degree of Protection
Pollution Class
Safety Class:
Overvoltage Category:
General
Dimensions (H x W x D)
Material:
Weight (including package) for -24 types
Dimensions
88 (3.5)
Doc: 70-00-0181, V3.0 Date: 20120424
Subject to alteration
conformity
EMC Directive
Low Voltage Directive
for -24 types
for -230 types
for -24 types
for -230 types
Front part:
Power case:
Cover, back part
Mounting Plate
for -120 and -230 types
© Vector Controls GmbH, Switzerland
TLC3-FCR-M Engineering Manual
-24
22-26V AC/DC
Max 1W, 1.5 VA
Terminal Connectors
Min 48h if charged for 24h
RT Internal, External (Sxx-Tn10 sensor)
0...50 °C (32...122 °F)
0.5°C (1°F)
DO1 to DO3
Relays
2A max. each output
For -230 types only
3750V AC to EN 60 730-1
1250V AC to EN 60 730-1
AO1, For TLC3-FCR-M4 AO2
DC 0...10 V
9.76 mV (10 bit)
10kOhm, 1mA.
To IEC 721-3-3
class 3 K5
0°C ...50°C (32°F...122°F)
<95% R.H. non-condensing
To IEC 721-3-2 and IEC 721-3-1
class 3 K3 and class 1 K3
-25°C...70°C (-13°F...158°F)
<95% R.H. non-condensing
class 2M2
2004/108/EC
2006/95/EC
EN 60 730 –1
EN 60 730 – 2 - 9
Emissions: EN 60 730-1
Immunity: EN 60 730-1
IP30 to EN 60 529
II (EN 60 730-1)
III (IEC 60 536)
II (IEC 60 536)
I (EN 60 730-1)
III (EN 60 730-1)
21 x 88 x 88mm (0.8 x 3.5 x 3.5 in.)
60 x 50 x 32mm (2.4 x 2.0 x 1.3 in)
ABS plastic (UL94 class V-0)
Galvanized Steel
standard: 260g (9.2oz), deluxe: 270g (9.5oz)
standard: 295g (10.5oz), deluxe: 305g (10.8oz)
32 (1.3)
21
Space required in flush mounting box:
(0.8)
(H x W x D)
60 x 50 x 32mm (2.4 x 2.0 x 1.26 in.)
Distance for mounting screws:
Horizontal and vertical:
45 to 63mm (1.8 to 2.5 in.)
-230
210–250 VAC
Page 2