PRE - INSTALLATION
LOCATION OF UNIT: The Model 190.81.12.32 (8100-A) Emergency Shower should be
installed in close proximity to potential accident areas. It should be clearly identified, free
from obstructions and easy to access.
SUPPLY LINE: The minimum recommended line size is 1-1/4" BSPT with 210 – 600 kPa
flowing pressure. Where sediment or mineral content is a problem, an inlet filter is
recommended.
PLUMBING CONNECTIONS: Inlet supply is male 1-1/4" BSPT.
Free Standing Drench Shower, Pull
MSR ABS Shower (HAWS)
th
Version 3.1, 13
Aug. 2021, Page 1 of 6

Advertisement

loading

Summary of Contents for Galvin Engineering GalvinSafe 190.81.12.32

  • Page 1 ® Rod, Axion MSR ABS Shower (HAWS) PRODUCT CODE: Galvin Engineering: 190.81.12.32 HAWS: 8100-A PRE - INSTALLATION LOCATION OF UNIT: The Model 190.81.12.32 (8100-A) Emergency Shower should be installed in close proximity to potential accident areas. It should be clearly identified, free from obstructions and easy to access.
  • Page 2: Parts Breakdown

    ITEM CODE DESCRIPTION 190.92.00.10 SHOWER HEAD 190.92.04.30 VALVE ASSEMBLY EMERGENCY SHOWER SAFETY SIGN* 190.92.30.20 PULL ROD FLOOR FLANGE* STRIPE TAPE* 190.91.80.33 TEST TAG * spare parts will require special order or may not be available (contact Galvin engineering for more details).
  • Page 3: Installation Procedure

    Version 3.1, 13 Aug. 2021, Page 3 of 6 INSTALLATION PROCEDURE Refer to Installation Drawing for clarification. Check parts list to ensure all required parts are included. Use an AS 4020 approved pipe joint sealant on all connections. STEP 1: Prepare the emergency shower foundation by using the floor flange as a template.
  • Page 4 Version 3.1, 13 Aug. 2021, Page 4 of 6 Version 3, 30 June...
  • Page 5: Troubleshooting

    Version 3.1, 13 Aug. 2021, Page 5 of 6 TROUBLESHOOTING PROBLEM REPAIR CHECKLIST 1. No Flow. Check the main shut-off valve. 2. a. Verify minimum 210 kPa flowing supply line pressure. 2. Insufficient water flow at shower b. Probable clogging of flow control inside shower head.
  • Page 6: Warranty