Outdoor Unit High Pressure Value and Outdoor Total Electric Current Curve (Heating)
Model Name : AS*B24LDC
[Condition]
Ambient
Indoor 15 - 23degC, Outdoor 2 - 12degC
temperature
Refrigerant
Standard amount
amount
Piping
7.5m (Height difference 1m)
length
Power
50Hz - 230V
voltage
Operation
TEST mode (Heating), Hi Fan, Lower direction, Front air flow
condition
Measuring
outdoor unit overall current with the current clamp meter at Power Cable.
method
Start operation with the condition of the Indoor Unit air filter clean.
Caution
[Constant Frequency Operation Method (Test mode)]
1. Operate on Heating mode, and press TEST button of remote control.
2. Operate continuously for 30 minutes. (After 60 minutes of operation, Test mode is released automatically.)
(1) Indoor/Outdoor Temperature - Outdoor High Pressure Curve
AS*B24LDC
4.0
3.8
3.6
3.4
3.2
3.0
2.8
2.6
2.4
2.2
2.0
0
2
4
Outdoor ambient temperature[ C]
(2) Indoor/Outdoor Temperature - Outdoor Total Electric Current Curve
AS*B24LDC
13.0
23 C
12.5
Indoor ambient
20 C
temperature[ C]
12.0
15 C
11.5
11.0
10.5
10.0
9.5
9.0
0
2
4
Outdoor ambient temperature[ C]
23 C
Indoor ambient
20 C
temperature[ C]
15 C
6
8
10
12
[50Hz-230V]
6
8
10
12
[50Hz-230V]
14
14
08-03