DHQ024-060
General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
Location. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Rigging And Handling . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
Ductwork . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Filters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Condensate Drain . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Service Access . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Thermostat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
Power And Control Wiring. . . . . . . . . . . . . . . . . . . . . . . . . 10
Compressors. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Gas Heat . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
1 Unit Limitations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Weights and Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Unit Accessory Weights . . . . . . . . . . . . . . . . . . . . . . . . . . 6
4 Unit Dimensions Front . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
5 Unit Clearances . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
6 Electrical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
7 DHQ024-060 Two Stage Gas Heat . . . . . . . . . . . . . . . . 12
8 Natural Gas Pipe Sizing Chart . . . . . . . . . . . . . . . . . . . . 14
9 Propane (LP) Gas Pipe Sizing Chart . . . . . . . . . . . . . . . 14
12 DHQ024-060 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
13 DHQ024-060 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
1 Component Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
2 Unit 4 Point Load Weight . . . . . . . . . . . . . . . . . . . . . . . . . 6
3 Unit Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
4 Dimensions Front and Bottom . . . . . . . . . . . . . . . . . . . . . 8
5 Dimensions Back and Bottom . . . . . . . . . . . . . . . . . . . . . 8
6 Roof Curb . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
7 Typical Field Control Wiring Diagram For Dual Fuel Heat
Pump . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

General

Unitary Products Model DHQ units are dual fuel heat pump
units designed for outdoor installation. Only gas piping, electric
power and duct connections are required at the point of
installation.
The two stage gas-fired heaters have spark to pilot ignition. The
tubular heat exchangers are aluminized steel.
The refrigerant system is fully charged with R-410A Refrigerant,
and is tested and factory sealed.

TABLE OF CONTENTS

Flue Vent Hood . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Airflow Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Bottom Duct Application . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Side Duct Application . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
Blower Speed Selection . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Sequence Of Operation . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Start-Up . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Adjustment of Temperature Rise . . . . . . . . . . . . . . . . . . . 30
Checking Gas Heat Input . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Natural Gas . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Typical Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Start-Up Sheet . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
LIST OF TABLES
14 Additional Static Resistance . . . . . . . . . . . . . . . . . . . . . . 22
15 Indoor Blower Specifications . . . . . . . . . . . . . . . . . . . . . . 23
16 Delay Profile . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
18 Ignition Control Board Flash Codes . . . . . . . . . . . . . . . . 28
19 Gas Rate Cubic Feet Per Hour . . . . . . . . . . . . . . . . . . . . 31
20 DHQ24 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . . 34
21 DHQ030 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . 34
22 DHQ036 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . 35
23 DHQ42 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . . 35
24 DHQ48 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . . 36
25 DHQ060 Charging Table . . . . . . . . . . . . . . . . . . . . . . . . 36
LIST OF FIGURES
8 Typical Field Power Wiring Diagram . . . . . . . . . . . . . . . 11
10 Flue Vent Outlet Air Hood . . . . . . . . . . . . . . . . . . . . . . . 14
11 Control Board Speed Tap Location . . . . . . . . . . . . . . . . 23
12 Two Stage Gas Valve Front . . . . . . . . . . . . . . . . . . . . . . 30
13 Two Stage Gas Valve Rear . . . . . . . . . . . . . . . . . . . . . . 30
14 Proper Flame Adjustment . . . . . . . . . . . . . . . . . . . . . . . 30
15 R-410A Quick Reference Guide . . . . . . . . . . . . . . . . . . 39
Safety Considerations
This is a safety alert symbol
labels or in manuals, be alert to the potential for personal injury.
Understand and pay particular attention the signal words
DANGER, WARNING or CAUTION.
DANGER indicates an imminently hazardous situation, which,
if not avoided, will result in death or serious injury.
WARNING indicates a potentially hazardous situation, which,
if not avoided, could result in death or serious injury.
CAUTION indicates a potentially hazardous situation, which, if
not avoided may result in minor or moderate injury. It is also
used to alert against unsafe practices and hazards involving
only property damage.
Management System
. When you see this symbol on
1101790-UIM-C-0414
SO 9001
Certified Quality

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the DHQ024 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for Johnson Controls Unitary Products DHQ024

  • Page 1: Table Of Contents

    24 DHQ48 Charging Table ......36 12 DHQ024-060 ........16 25 DHQ060 Charging Table .
  • Page 2 Follow the gas supplier’s instructions. d. If you cannot reach your gas supplier, call the fire department. Installation and service must be performed by a qualified installer, service agency or the gas supplier. Johnson Controls Unitary Products...
  • Page 3: Installation

    National Electrical Code, ANSI/NFPA No. 70 - Latest Edition specified on the unit name/rating plate, specified on Page 17 of these instructions. National Fuel Gas Code, ANSI Z223.1 - Latest Edition Johnson Controls Unitary Products...
  • Page 4: Unit Limitations

    Figure 1: Component Location Table 1: Unit Limitations Unit Limitations Model Unit Voltage Applied Voltage Outdoor DB Temp (Tons) Max (°F) DHQ024 208/230-1-60 (2.0) DHQ030 208/230-1-60 (2.5) DHQ036 208/230-1-60 (3.0) DHQ042 208/230-1-60 (3.5) DHQ048 208/230-1-60 (4.0) Johnson Controls Unitary Products...
  • Page 5: Location

    The condenser coils should be protected from rigging 7.3, or 7.4 of Gas Installation Codes, CSA-B149.1 (in Canada) - cable damage with plywood or other suitable material. Latest Edition, and/or applicable provisions of the local building Johnson Controls Unitary Products...
  • Page 6: Weights And Dimensions

    20.1 (2.0) DHQ030 24.4 20.1 (2.5) DHQ036 24.6 20.1 (3.0) DHQ042 25.1 20.4 (3.5) DHQ048 25.3 20.8 (4.0) DHQ060 25.5 20.5 (5.0) Table 3: Unit Accessory Weights Weight (lbs.) Unit Accessory Model Shipping Operating Add Economizer Johnson Controls Unitary Products...
  • Page 7: Unit Dimensions Front

    COMPARTMENT PANEL 47-1/4 (OVERALL) (OVERALL) 2-5/8 3-1/3 Unit Dimensions Figure 3: Table 4: Unit Dimensions Front Dimensions Unit Model “A” “B” DHQ024, 030, 036 33-1/2 18-1/4 DHQ042, 048, 060 41-1/2 23-1/8 Table 5: Unit Clearances Distance Distance Direction Direction (in.) (in.)
  • Page 8: Dimensions Front And Bottom

    SIDE SUPPLY 14-1/2 AIR OPENING *CONDENSER 28-3/8 COIL 14-1/2 BACK BOTTOM SUPPLY AIR OPENING 3-3/8 SIDE RETURN AIR OPENING 14-1/2 4-1/4 1-3/4 1-3/4 BOTTOM RETURN 28-9/16 3-1/2 AIR OPENING 1-3/4 Figure 5: Dimensions Back and Bottom Johnson Controls Unitary Products...
  • Page 9: Ductwork

    Filters should be checked monthly; this is especially important NOTE: Be sure to note supply and return openings. since this unit is used for both heating and cooling. 1. 8” Roof Curb also available. Johnson Controls Unitary Products...
  • Page 10: Condensate Drain

    Refer to Figures thru 8 for typical field wiring and to the appropriate unit wiring diagram for control circuit and power wiring information. Johnson Controls Unitary Products...
  • Page 11: Electrical Data

    (3.5) DHQ048 208/230-1-60 21.1 38.3 (4.0) DHQ060 208/230-1-60 28.8 (5.0) 1. Minimum Circuit Ampacity. 2. Maximum Over Current Protection per standard UL 1995. 3. Fuse or HACR circuit breaker size installed at factory or field installed. Johnson Controls Unitary Products...
  • Page 12: Dhq024-060 Two Stage Gas Heat

    1101790-UIM-C-0414 Table 7: DHQ024-060 Two Stage Gas Heat Models Component DHQ024 DHQ030 DHQ036 DHQ042 DHQ048 DHQ060 Nominal Tonnage AHRI COOLING PERFORMANCE Gross Capacity @ AHRI A point (MBH) 23.7 30.1 37.2 43.5 47.7 55.0 AHRI net capacity (MBH) 22.8 29.0 34.6...
  • Page 13: Compressors

    Units are shipped with compressor mountings which are factory-adjusted and ready for operation. 1/2” - NPTF DRIP LEG Do not loosen compressor mounting bolts. Figure 9: External Supply Connection External Shut-Off Johnson Controls Unitary Products...
  • Page 14: Natural Gas Pipe Sizing Chart

    The gas supply should be a separate line and installed in cycle. Flue hood surface and the immediate area reach accordance with all safety codes as prescribed under high temperatures during the heating cycle. Limitations, shown on Page 3. After the gas connections Johnson Controls Unitary Products...
  • Page 15: Ton

    4% for each 1,000 feet above sea level. 3. Based on 2500 BTU/Ft. 4. The air flow must be adequate to obtain a temperature rise within the range shown. Continuous return air temperature should not be below 55°F. Johnson Controls Unitary Products...
  • Page 16: Dhq024-060

    1101790-UIM-C-0414 Airflow Performance Bottom Duct Application Table 12: DHQ024-060 External Static Pressure (Inch Water Gauge) Model Thermostat Speed Mode (Tons) Input Watts Watts Watts Watts Watts Watts Watts Watts Watts Y1+O COOL-A Y1+O COOL-B Y1+O COOL-C Y1+O COOL-D Cool Y1+Y2+O...
  • Page 17 1101790-UIM-C-0414 Table 12: DHQ024-060 (Continued) External Static Pressure (Inch Water Gauge) Model Thermostat Speed Mode (Tons) Input Watts Watts Watts Watts Watts Watts Watts Watts Watts Y1+O COOL-A Y1+O COOL-B Y1+O COOL-C Y1+O COOL-D Cool Y1+Y2+O COOL-A 1100 Y1+Y2+O COOL-B...
  • Page 18 1101790-UIM-C-0414 Table 12: DHQ024-060 (Continued) External Static Pressure (Inch Water Gauge) Model Thermostat Speed Mode (Tons) Input Watts Watts Watts Watts Watts Watts Watts Watts Watts Y1+O COOL-A Y1+O COOL-B Y1+O COOL-C 1101 Y1+O COOL-D 1301 Cool Y1+Y2+O COOL-A 1450...
  • Page 19: Dhq024-060

    1101790-UIM-C-0414 Side Duct Application Table 13: DHQ024-060 External Static Pressure (Inch Water Gauge) Model Thermostat Speed Mode (Tons) Input Watts Watts Watts Watts Watts Watts Watts Watts Watts Y1+O COOL-A Y1+O COOL-B Y1+O COOL-C Y1+O COOL-D Cool Y1+Y2+O COOL-A Y1+Y2+O...
  • Page 20 1101790-UIM-C-0414 Table 13: DHQ024-060 (Continued) External Static Pressure (Inch Water Gauge) Model Thermostat Speed Mode (Tons) Input Watts Watts Watts Watts Watts Watts Watts Watts Watts Y1+O COOL-A Y1+O COOL-B Y1+O COOL-C Y1+O COOL-D Cool Y1+Y2+O COOL-A 1100 Y1+Y2+O COOL-B...
  • Page 21 1101790-UIM-C-0414 Table 13: DHQ024-060 (Continued) External Static Pressure (Inch Water Gauge) Model Thermostat Speed Mode (Tons) Input Watts Watts Watts Watts Watts Watts Watts Watts Watts Y1+O COOL-A Y1+O COOL-B Y1+O COOL-C 1101 Y1+O COOL-D 1301 Cool Y1+Y2+O COOL-A 1450...
  • Page 22: Additional Static Resistance

    1. The pressure drop through the economizer is greater for 100% outdoor air than for 100% return air. If the resistance of the return air duct is less than 0.25 IWG, the unit will deliver less CFM during full economizer operation. Johnson Controls Unitary Products...
  • Page 23: Blower Speed Selection

    “A” from the factory. 24 Volts AC is also sent out of the CFMCB to the ECM Blower Motor for first stage cooling fan speed and out of the “RV” and Johnson Controls Unitary Products...
  • Page 24 “Y1” terminal of the YorkGuard VI 30 seconds before defrost is initiated. This allows the heat Defrost Control Board (DCB) energizing the “M1” contactor coil. exchanger time to begin warming up prior to reversing refrigerant flow. Johnson Controls Unitary Products...
  • Page 25 “RV” and “RVG” terminals de-energizing the Same as when Outdoor Ambient Temperature is above reversing valve. The “ODF” contacts on the DCB re-close Balance Point as previously discussed. energizing the outdoor fan motor. Mechanical heating operation resumes. Johnson Controls Unitary Products...
  • Page 26 120 Volts AC out of the “H-IND” terminal and remove 120 Volts approximately 60 seconds. AC from the “IND” terminal energizing the DM at high speed. Johnson Controls Unitary Products...
  • Page 27: Dual Fuel Package Unit Operating Chart

    No Heat until overridden by No Heat until overridden by Defrost Control Board (DCB) the 4 hour pipe freeze timer the 4 hour pipe freeze timer “W2 Out” “W2 Out” after 15 Minutes after 15 Minutes Johnson Controls Unitary Products...
  • Page 28: Ignition Control Board Flash Codes

    "9" on the 8 Flashes Flame present with gas off LED. If the pilot or main valve becomes Un-Welded the inducer 9 Flashes Gas valve stuck OFF or ON 10 Flashes Flame sense circuit failure Johnson Controls Unitary Products...
  • Page 29: Start-Up

    Small adjustments to the gas flow may be made by turning the Operating Instructions pressure regulator adjusting screw on the automatic gas valve. Refer to Figures 14 and 12. STOP! Read the information on the unit safety label. Johnson Controls Unitary Products...
  • Page 30: Adjustment Of Temperature Rise

    SHUT-OFF VALVE AND SHUT OFF ALL POWER TO THE thru 11. UNIT. Remove the two (2) #8 screws holding each burner in place. After the temperature rise has been determined, the CFM can be calculated as follows: Johnson Controls Unitary Products...
  • Page 31: Checking Gas Heat Input

    Multiply 95 x 1050 (the BTU rating of the gas obtained from the local gas company). The result is 99,750 BTUH, which is close to the 100,000 BTUH rating of the furnace. Johnson Controls Unitary Products...
  • Page 32: Typical Wiring Diagrams

    1101790-UIM-C-0414 Typical Wiring Diagrams Typical DHQ024 Heat Pump with Two Stage Gas Heat 208/230-1-60 volt Wiring Diagram Johnson Controls Unitary Products...
  • Page 33 1101790-UIM-C-0414 Typical DHQ030-060 Heat Pump with Two Stage Gas Heat 208/230-1-60 volt Wiring Diagram Johnson Controls Unitary Products...
  • Page 34: Dhq24 Charging Table

    Pressure Temp. Pressure Temp. Evap Db Evap Db Amps 300 Cfm/Ton 80/62 300 Cfm/Ton 80/67 10.0 300 Cfm/Ton 80/72 300 Cfm/Ton 75/63 11.2 400 Cfm/Ton 80/62 400 Cfm/Ton 80/67 10.0 400 Cfm/Ton 80/72 400 Cfm/Ton 75/63 Johnson Controls Unitary Products...
  • Page 35: Dhq036 Charging Table

    10.4 300 Cfm/Ton 11.7 80/72 13.1 10.0 300 Cfm/Ton 11.3 75/63 12.8 10.9 400 Cfm/Ton 11.3 80/62 12.7 11.1 400 Cfm/Ton 11.5 80/67 13.0 11.3 400 Cfm/Ton 11.7 80/72 13.2 11.0 400 Cfm/Ton 12.4 75/63 14.1 Johnson Controls Unitary Products...
  • Page 36: Dhq48 Charging Table

    16.0 300 Cfm/Ton 17.1 80/72 18.8 15.3 300 Cfm/Ton 17.0 75/63 19.1 15.6 400 Cfm/Ton 16.8 80/62 18.6 15.9 400 Cfm/Ton 17.0 80/67 18.8 16.2 400 Cfm/Ton 17.3 80/72 19.0 15.6 400 Cfm/Ton 17.4 75/63 19.5 Johnson Controls Unitary Products...
  • Page 37: Start-Up Sheet

    Outside air dry bulb temperature Return static (inches of water column) Return air dry bulb temperature Return air wet bulb temperature Total external static pressure Temperature drop Supply air wet bulb temperature Page 1 of 2 Johnson Controls Unitary Products...
  • Page 38 Provide owner with the owner's manual Explain operation of system to equipment owner Explain thermostat use and programming (if applicable) to owner Explain the importance of regular filter replacement and equipment maintenance Comments and Additional Job Details Page 2 of 2 Johnson Controls Unitary Products...
  • Page 39: 410A Quick Reference Guide

    Never open system to atmosphere when under a vacuum. If system must be opened for service, evacuate system the break the vacuum with dry nitrogen and replace all filter driers. Figure 15: R-410A Quick Reference Guide Johnson Controls Unitary Products...
  • Page 40 Subject to change without notice. Printed in U.S.A. 1101790-UIM-C-0414 Copyright © 2014 by Johnson Controls, Inc. All rights reserved. Supersedes: 1101790-UIM-B-0314 York International Corporation 5005 York Drive Norman, OK 73069...