General Specifications (Control)

The general (control) specifications are shown in the following table.
General Control Specifications
Item
Maximum output frequency
Speed sensor (PG pulse output)
Basic control
Basic control
performance
system
Operation control
range
Field weakening
control
Speed accuracy
Speed resolution
Acceleration/deceler
ation time
Operation
Restart after
specification
instantaneous
interruption
Communicati
Serial interface
ons
Commissioning/Mai
ntenance Tool
Cubicle
LED 1 lamp
display/
operation
LED 2 lamp
LCD display
Operation apparatus Backlit type interlock switch: 1
Connector
IF08CZ9 September, 2019
Toshiba Reference File #328
Standard specification
75 Hz
No
Induction Motor Volts/Hertz
3%-100%
1:1.5
±0.5%
1/25000
(Digital setting)
0.1 – 3276.7 sec,
acceleration/deceleration
independent setting
Possible
(more than 5 cycles interruption
causes shut down)
None
Ethernet (with modular jack attached
to keypad)
READY: Operation preparation
completed(Green)
RUN: Inverter in operation(Red)
ALARM/FAULT:
Alarm slow flashing/Fault fast flashing
ON - Keypad control
OFF - Other than keypad control
128x64 Pixel Graphical LCD display
Unlit reset switch: 1
Operation via 8 key keypad and a
15pulse/30detent incremental
encoder
Personal computer connection
Ethernet modular jack
- 16 -
Option
Remarks
120 Hz
Yes
Induction Motor
Sensor type vector
Sensor Type Vector
control uses a 1x
resolver or a PG.
Induction Motor
The maximum PG
Sensorless Vector
freq. is 100kHz.
1%-100%
Limited by motor
heating
1:5
Vector Control
±0.01%
Analog setting
1/1000. Isolation
transducer
recommended.
Most drives cannot
regenerate.
Under-voltage trip at
75% level
MODBUS
Requires optional
DEVICE_NET
board.
PROFIBUS
TL-S20
READY and RUN
light colors can be
reversed by changing
an EOI parameter

Advertisement