Safety Control Drawing

Position
Description
1
RX – LC connector interface for fibre - PORT B
TX – LC connector interface for fibre - PORT B
2
3
RX – LC connector interface for fibre - PORT C
TX – LC connector interface for fibre - PORT C
4
5
Screen/Shield RS-485/ARCNET - PORT B or C
6
In / Out / + line RS-485/ARCNET - PORT B or C
7
In / Out / - line RS-485/ARCNET - PORT B or C
8
Screen/Shield RS-485/ARCNET - PORT A1 (Panel IN Port)
9
In / Out / + line RS-485/ARCNET - PORT A1 (Panel IN Port)
10
In / Out / - line RS-485/ARCNET - PORT A1 (Panel IN Port)
11
Screen/Shield RS-485/ARCNET - PORT A2 (Panel OUT Port)
12
In / Out / + line RS-485/ARCNET - PORT A2 (Panel OUT Port)
13
In / Out / - line RS-485/ARCNET - PORT A2 (Panel OUT Port)
DNX R-2F Configuration
Position
Description
1
In / +Voltage A
2
In / Common
3
In / +Voltage B
4
In / Common
5
Earth connection
6
In & out / Relay contact (C - Common)
7
In & out / Relay contact (NC - Normally Closed)
8
In / Out / - line RS-485 – IO Interface
9
In / Out / + line RS-485 – IO Interface
10
Screen/Shield RS-485 – IO Interface
5
Table 3
DNX R-2FC Configuration
Figure 1
Table 4
Input / Output values
Data rate: 100 Mb/s –125 MBd.
Fibre drive distance:
M: Multi-mode - up to 2km
S: Single-mode – 10 / 15 / 20 /
40 / 80km variants
M: 850nm / 1310nm
S: 1310 / 1550nm
BiDi: 1310 & 1550nm
Umax = ± 5Vpk
Imax = ± 60 mA
Data rate:
4.8 to 115.2 kbit/s
Input / Output values
Uin = (18 –36): 24 VDC Nominal
Iin = 210 mA Rated at 24 VDC
Uin = 30 VDC max
Iin = 2000 mA max, Pin = 60 W max
Umax = ± 5Vpk
Imax = ± 60 mA
Data rate:
4.8 to 115.2 kbit/s
DNX-R-2F/FC-K