Install the refrigerated display cabinets on an even horizontal surface, if necessary, use adjustable legs to
level up the product. The refrigerated display cabinets should not tilt, incomplete alignment can result in deteri-
oration of the product work.
If the refrigerated display cabinets has wheels, they must be fixed after the product installation.
DO NOT install the refrigerated display cabinets in the following places (Fig. 3):
in close proximity to heat sources (e.g. heating batteries, equipment for food heating or cooking);
near the doors or in a draft caused by opening of the doors or windows;
in areas where strong air movement is possible (e.g. outlets of climatic, ventilation and heating
systems);
exposed to direct sunlight.
Air movement at a speed of over 0,2 m/sec in the area of the refrigerated display cabinets installation
deteriorates its operating characteristics.
Install the refrigerated display cabinets in such a way as to ensure free air circulation in the unit compart-
ment. Ensure a free zone of no less than 15 cm from the back wall of the refrigerated display cabinets to discharge
warm air from the condenser.
DO NOT place in the unit compartment any foreign objects that impede normal cooling of the refriger-
ating unit.
When arranging the refrigerated display cabinets at fuels and lubricants facilities, it must be installed and
operating rules at fuels and lubricants facilities. According to the requirements of UL 471, the refrigerated
display cabinets charged with a highly flammable refrigerant must be arranged at the level of no less than 18
inches (450 mm)0 above ground level at fuels and lubricants facilities.
According to the requirements of EN 378-1-2014, for refrigerated display cabinets charged with a flammable
refrigerant (e.g. R290) a minimum volume of premises is specified based on the lower flammability limit. For
example, the minimum volume of the room where the refrigerated display cabinets charged with R290 can be
arranged is 12,5 m
charged with a flammable refrigerant are located in one room, their charge values are summed up and the
volume of the room is selected accoding to their total charge (charge values are indicated on the nameplates).
In case of non-compliance with the refrigerated display cabinets installation rules, its operating charac-
teristics may differ from those stated.
www.beer-co.com

5. ARRANGEMENT REQUIREMENTS

Figure 3 – Arrangement of the refrigerated display cabinets
3
for every 100 g of the charged refrigerant. If a number of refrigerated display cabinetss