SPRINKLER HEAD
Concealed Sprinkler
MODEL: SD1050, SD1055
DESCRIPTION
The SHIELD Sprinklers, SD1050, SD1055 (Glass Bulb Type)
Standard and Quick Response Concealed Sprinkler, design
incorporates state-of-the-art, heat responsive, frangible glass
bulb design for prompt, precise operation. The die cast frame is
more streamlined and attractive than traditional sand cast frames.
It is cast with a hex-shaped wrench boss to allow easy tightening
from many angles, reducing assembly effort. This sprinkler is
available in various temperature ratings and finishes to meet
many design requirements. The recessed pendent should be
utilized with a recessed escutcheon which provides up ½" of
adjustments. All sprinklers are manufactured using the time
proven Belleville seal used exclusively by all major manufactures
to ensure long life and safe operation.
SPRINKLER OPERATION
The operating mechanism is a frangible glass bulb which contains
a heat responsive liquid. During a fire, the ambient temperature
rises causing the liquid in the bulb to expand. When the ambient
temperature reaches the rated temperature of the sprinkler, the
bulb shatters.
As a result, the waterway is cleared of all sealing parts and water
is discharged towards the deflector. The deflector is designed to
distribute the water in a pattern that is most effective in controlling
the fire.
MAXIMUM COVERAGE
Standard spray coverage is up to: Light Hazard = 225 square
feet(20.9 sq.m); Ordinary Hazard = 130 square feet(12.1 sq.m) per
NFPA 13.
RATINGS
Sprinkler Temperature
Classification
Ordinary
Intermediate
Intermediate
www.shieldglobal.com
Norminal Sprinkler
N.F.P .A Maximum Ambient
Temperature Rating
155ºF/68ºC
175ºF/79ºC
200ºF/93ºC
TECHNICAL SPECIFICATION
Sprinkler Identification
Number
Style
K Factor
Response Time Index
(RTI)
Nominal Thread Size
Orifice Size
Max. Working Pressure
Factory Hydrostatic Test 100%@500PSI(3450 kPa)
Min. Operation Pressure
Note: Shield SD1055 (3-mm bulb) is FM Approved
as standard response only. Factory Mutual do not
approve any concealed sprinklers for quick response
(Ceiling) Temp.(Allowed)
100ºF/38ºC
150ºF/65ºC
150ºF/65ºC
Standard SD1050 (bulb
5mm), Quick Response
SD1055 (bulb 3mm)
Concealed Sprinkler
½
½
5.6gpm/psi
. (80lpm/bar
)
Standard 50
Quick Response 30
½"NPT(15mm)
13mm
175PSI(1200kPa)
7 PSI(48 kPa)
Glass Bulb Color
Red
Yellow
Green
21

Advertisement

loading
Need help?

Need help?

Do you have a question about the SD1050 and is the answer not in the manual?

Questions and answers

Summary of Contents for Shield SD1050

  • Page 1 SPRINKLER HEAD Concealed Sprinkler MODEL: SD1050, SD1055 DESCRIPTION The SHIELD Sprinklers, SD1050, SD1055 (Glass Bulb Type) Standard and Quick Response Concealed Sprinkler, design incorporates state-of-the-art, heat responsive, frangible glass bulb design for prompt, precise operation. The die cast frame is more streamlined and attractive than traditional sand cast frames.
  • Page 2 PART LIST SD1050 SD1055 1. Frame 2. Deflector 3. Cap 4. Cap Seat 5. Load Screw 6. Seal 7. Bulb DISCHARGE CURVE www.shieldglobal.com...
  • Page 3 WARNINGS INSTALLATION SEQUENCE The SHIELD Sprinklers must be installed and maintained Step 1. The unit must be installed in the Pendent position in compliance with this document. Depressurize and drain for the Concealed Sprinkler. the piping system before attempting to install, remove, or adjust any Sprinklers.
  • Page 4 DISTRIBUTION PATTERNS K5.6 PENDENT SPRINKLER DISTRIBUTION PATTERNS - TRAJECTORY DIMENSIONS www.shieldglobal.com...