10-3. Address Setup (Manual Setting from Remote Controller)

In case that addresses of the indoor units will be
determined prior to piping work after wiring work
• Set an indoor unit per a remote controller.
• Turn on power supply.
1
Push
+
+
seconds or more.
2
(Line address)
Using the temperature setup
set 12 to the CODE No.
3
Using timer time
4
Push
button. (OK when display goes on.)
5
(Indoor unit address)
Using the temperature setup
6
Using timer time
7
Push
button. (OK when display goes on.)
8
(Group address)
Using the temperature setup
9
Using timer time
Follower unit.
10
Push
button. (OK when display goes on.)
11
Push
button.
Setup completes. (The status returns to the usual stop status.)
2, 5, 8
END
<Operation procedure>
1
2
Indoor unit address → 1
buttons simultaneously for 4
/
/
buttons, set the line address.
/
/
buttons, set 1 to the line address.
/
/
buttons, set
TEMP.
11
FILTER
L L
RESET
1
3
4
5
(Example of 2-lines wiring)
(Real line: Wiring, Broken line: Refrigerant pipe)
Outdoor
1 2 3
1 2 3
Indoor
A B
Line address → 1
Group address → 1
A B
Remote controller
buttons,
13 13 13 13 13
buttons, set
to the CODE No.
14 14 14 14 14
buttons, set
to the CODE No.
0000
0000
0000
0001
0001
0001
0000
0000
to Individual,
0001
0001
ON / OFF
TIMER SET
FAN
MODE
TIME
SAVE
A A
VENT
TEST
SET
CL
SWING/FIX
UNIT LOUVER
T
6
7
8
9
– 92 –
Outdoor
1 2 3
1 2 3
Indoor
Indoor
A B
A B
1
1
2
3
2
2
For the above example, perform setting by
connecting singly the wired remote controller
without remote controller inter-unit wire.
Group address
Individual
: 0000
Header unit : 0001
In case of group control
Follower unit : 0002
to Header unit, and
3, 6, 9
4, 7, 10
10
11
END
1 2 3
1 2 3
1 2 3
Indoor
Indoor
A B
A B
2
2
1
2
2
2
0002
0002
0002
0002
0002
to