1. SPECIFICATIONS

SDI combination (R32)
<Single type>
Model name
Indoor Unit
Outdoor Unit
Cooling capacity (Rated (Min.-Max.))
Heating capacity (Rated (Min.-Max.))
Power supply
Electrical
Cooling
characteristics
(*1)
Heating
Maximum current
Appearance
Main Unit
Ceiling panel
(Sold Separately)
Outer dimension Main unit
Ceiling panel
(Sold Separately)
Weight
Main unit
Ceiling panel (Sold Separately)
Heat exchanger
Fan unit
Fan
Standard air flow ( M+ / M / L+ / L )
Motor
Air filter
Drain port (Nominal dia. mm)
Sound pressure level High ( M+ / M / L+ / L )
Sound power level High ( M+ / M / L+ / L ) (*2)
Refrigerant ( Type / Charge weight (kg) )
Outer dimension
Weight
Sound pressure level
Sound power level
Pipe connections
Operation Range
*1 : The Cooling capacity and electrical characteristics are measured under the conditions specified by JIS B
8615-1 based on the reference piping.
The reference piping consists of 5m of main piping and 2.5m of branch piping connected with 0 meter
height.
*2 : The sound level are measured in an anechoic chamber in accordance with JIS B 8616. Normally, the
values measured in the actual operation environment become larger than the indicated values due to the
effects of external sound.
*3 : Height from the ceiling. Depth doesn't include the electric parts box.
Notes ;
Rated conditions Cooling : Indoor air temperature 27°CDB/ 19 °CWB, Outdoor air temperature 35°CDB
Heating : Indoor air temperature 20°CDB, Outdoor air temperature 7°CDB/ 6°CWB
RAV-RM
RAV-GP
Running current
Power consumption
Power factor
EER
Running current
Power consumption
Power factor
COP
Indoor Unit
Model name
Color
H x W x D (*3)
H x W x D (*3)
Outdoor Unit
H x W x D
Cooling/Heating
Cooling/Heating
Gas / Liquid
Min. Length
Max. Length
Chargeless
Max. height difference
Cooling
Heating
kW
kW
1 phase 50Hz 230V (220V-240V)
A
kW
%
A
kW
%
A
Zinc hot dipping steel plate
* Heat-insulating material attached to only upper plate
Gran White (Mansell 5PB9/1)
mm
mm
kg
kg
m³/h
798 (720 / 672 / 562 / 546)
W
Standard filter (Long life filter)
VP20 (Polyvinyl chloride tube)
dB(A)
dB(A)
mm
kg
dB(A)
dB(A)
mm
m
m
m
m
˚C
˚C
– 19 –
561MUT-E
561ATP-E
5.0 (1.2-5.6)
5.6 (0.9-7.0)
7.49 - 6.87
1.56
94
3.21
7.68 - 7.04
1.60
95
3.5
13.1
RBC-UM21PG(W)-E
256 x 575 x 575
12 x 620 x 620
15.0
2.5
Finned tube
Turbo fan
60
44 ( 42 / 39 / 36 / 35 )
59 ( 57 / 54 / 51 / 50 )
R32/1.35
630 x 799 x 299
45
46 / 48
63 / 65
12.7 / 6.4
3
50
20
30
–15 to 52
–27 to 15