Recommended Heights For Woodstove Flue; Mobile Home Installation - Regency F1104S Owners & Installation Manual

Table of Contents

Advertisement

installation
16 |
MINIMUM RECOMMENDED FLUE HEIGHTS IN FEET
ELEVATION (FT)
ABOVE SEA LEVEL
0-1000
1000-2000
2000-3000
3000-4000
4000-5000
5000-6000
6000-7000
7000-8000
8000-9000
9000-10000
NOTE: No more than two offsets (four elbows) allowed. Two 45
RECOMMENDED
HEIGHTS FOR
WOODSTOVE FLUE
Simple rules on draft. See Table 1.
1) At sea level minimum height is 12' straight.
2) Add the following vertical height to compen-
sate for:
45 deg. elbow
= 1 ft.
90 deg. elbow
= 2 ft.
"T"
= 3 ft.
Each foot of horizontal run = 2 ft.
3) Add 4% overall for each 1000' above sea
level.
Example: a)
1-1/2 ft. of horizontal run
one "T"
Total Addition (at sea level)
Example: b)
One 90 deg. elbow
2 ft. of horizontal run
one "T"
Total Addition (at sea level)
Recommended Flue Height
Elevation
Example a)
0'
18'
1000'
18.72'
2000'
19.44'
5000'
21.60'
8000'
23.76'
16
| F1104S / F3104L Freestanding Woodstove
(Measured from the top of the unit)
0
12.0
12.5
13.0
13.5
14.0
14.5
15.0
15.5
16.0
16.5

MOBILE HOME INSTALLATION

Once you have properly marked the position
of your unit and the floor protection as outlined
in the Residential Installation items #1 through
#8, a supply of fresh air has to be supplied to
your unit. Cut a minimum 4 inch diameter hole
through your floor protector and the floor directly
under your pedestal base to the outside. Use
4" duct pipe with a mesh grill to pipe fresh air
into the pedestal area. Block off the hole in the
back of the pedestal with the square plate and
the two 1/2" screws provided.
Place your unit in position and secure it to the
floor using two lag bolts 3/8" x 3-1/2" through
the two holes inside the pedestal base. It is
important to maintain the structural integrity
of the Mobile Home floor, walls and roof when
installing your unit.
= 3 ft.
= 3 ft.
For Mobile Home units installed in the U.S. the
= 6 ft.
unit must be grounded using a #8 ground wire
with approved termination and star washer.
= 2 ft.
= 4 ft.
= 3 ft.
Minimum height requirements
= 9 ft.
must be met. Safe removal of
the chimney system must be
adhered to when transporting the
Example b)
mobile home.
21'
21.84'
22.68'
25.20'
27.72'
WARNING: Operate only with door fully
closed - open feed door to feed fire only.
TABLE 1
# OF ELBOWS
2 x 15
4 x 15
2 x 30
o
o
13.0
14.0
15.0
13.5
14.5
15.5
14.0
15.0
16.0
14.5
15.5
17.0
15.0
16.0
17.5
15.5
17.0
18.0
16.0
17.5
18.5
16.5
18.0
19.0
17.0
18.5
20.0
17.5
19.0
20.5
elbows equal one 90
o
WARNING:
4 x 30
2 x 45
4 x 45
o
o
o
18.0
16.0
20.0
19.0
16.5
21.0
19.5
17.0
21.5
20.0
18.0
22.5
21.0
18.5
23.0
21.5
19.0
24.0
22.5
20.0
25.0
23.0
20.5
25.5
24.0
21.0
26.5
24.5
22.0
27.0
elbow.