Temperature Limit Switch Usage For Gas; Heat Units - Trane YSC036G Installation, Operation And Maintenance Manual

Packaged rooftop air conditioners precedent - gas/electric 3 to 10 tons - 60 hz
Table of Contents

Advertisement

Temperature Limit Switch Usage for Gas

Heat Units

Units are factory shipped in the downflow discharge
configuration but can be field converted to a horizontal
discharge configuration. Some, but not all units require a
different TCO1 limit switch, which is attached to the
combustion blower motor if horizontal discharge
configuration is used.
If any of the units are installed in the downflow discharge
configuration and have the alternate TCO1 limit switch
provided, remove the additional TCO1 limit switch from
the combustion blower motor and discard.
Table 5.
TC01 tripping values
Unit Model - 6 to 10 Ton
Standard Efficiency
YSC072H**(M,Y)
YSC072H**(L,X)
YSC072H**(H,Z)
YSC090H**(L,X)
YSC090H**(M,Y)
YSC090H**(H,Z)
(a)
YSC092H**(L,X)
(b)
YSC092H**(L,X)
YSC092H**(M,Y)(a)
YSC092H**(M,Y)(b)
YSC092H**(H,Z)(a)
YSC092H**(H,Z)(b)
YSC102H**(L,X)(a)
YSC102H**(L,X)(b)
YSC102H**(M,Y)(a)
YSC102H**(M,Y)(b)
YSC102H**(H,Z)(a)
YSC102H**(H,Z)(b)
YSC120H**(L,X)
YSC120H**(M,Y)
YSC120H**(H,Z)
(a) Digit 15 = 0,1
(b) Digit 15 = 6,7
Table 6.
TC01 tripping values
Unit Model - High Efficiency
15 SEER
YHC036E**(L,X)-DD
YHC036E**(L,X)-BD
YHC036E1*(M,Y)-DD
YHC036E(3,4,W)*(M,Y)-DD
YHC036E**(M,Y)-BD
YHC036E1*(H,Z)-DD
YHC036E(3,4,W)*(H,Z)-DD
YHC036E**(H,Z)-BD
YHC048F1*(L,X)-DD
YHC048E/F(3,4,W)*(L,X)-DD
YHC048E/F**(L,X)-BD
RT-SVX21AC-EN
TCO1 Tripping Values -
Downflow/ Horizontal
155F/170F
170F
145F/155F
180F/200F
155F
155F
200F/220F
225F
230F
190F/225F
220F/260F
220F/260F
200F/220F
225F
230F
190F/225F
220F/260F
220F/260F
190F/225F
200F
150F/210F
(a),(b)
TCO1 Tripping Values -
Downflow/ Horizontal
180F
170F
190F
170F/190F
180F/190F
190F/220F
170F/190F
155F/190F
170F/155F
145F/155F
155F
Table 6.
TC01 tripping values
Unit Model - High Efficiency
15 SEER
YHC048F1*(M,Y)-DD
YHC048E/F(3,4,W)*(M,Y)-DD
YHC048E/F**(M,Y)-BD
YHC048F1*(H,Z)-DD
YHC048E/F(3,4,W)*(H,Z)-DD
YHC048E/F**(H,Z)-BD
YHC060F1*(L,X)-DD
YHC060E/F(3,4,W)*(L,X)-DD
YHC060E/F**(L,X)-BD
YHC060F1*(M,Y)-DD
YHC060E/F(3,4,W)*(M,Y)-DD
YHC060E/F**(M,Y)-BD
YHC060F1*(H,Z)-DD
YHC060E/F(3,4,W)*(H,Z)-DD
YHC060E/F**(H,Z)-BD
YHC072E/F**(L,X)
YHC072E/F**(M,Y)
YHC072E/F**(H,Z)
YHC074F**(L,X)
YHC074F**(M,Y)
YHC074F**(H,Z)
YHC092F**(L,X)
YHC092F**(M,Y)
YHC092F**(H,Z)
YHC102F**(L,X)
YHC102F**(M,Y)
YHC102F**(H,Z)
YHC120F**(L,X)
YHC120F**(M,Y)
YHC120F**(H,Z)
(a) BD= Belt drive ID motor
(b) DD= Direct drive ID motor
Table 7.
TC01 tripping values
Unit Model - High Efficiency
17 Plus
YHC037***(L,X)
YHC037***(M,Y)
YHC037***(H,Z)
YHC047***(L,X)
YHC047***(M,Y)
YHC047***(H,Z)
YHC067***(L,X)
YHC067***(M,Y)
YHC067***(H,Z)
Installation
(a),(b)
(continued)
TCO1 Tripping Values -
Downflow/ Horizontal
140F
150F/170F
170F/180F
180F/200F
220F
220F/260F
155F
140F
155F/145F
140F/150F
145F/170F
170F
180F
190F/220F
220F/230F
200F
220F
210F
170F
180F/190F
180F/230F
200F/220F
190F/225F
200F
200F/220F
190F/225F
200F
170F/200F
170F/190F
135F/155F
TCO1 Tripping Values -
Downflow/ Horizontal
190F
170F/220F
220F
145F/155F
170F
220F
140F
170F
170F
31