(16) Emergency response operating mode
The emergency operation mode is a mode in which the unit is run in an emergency to respond to the trouble when
the
compressors (No. 1, No. 2) break down, making it possible to carry out a trouble reset using the remote control.
1) Starting the Emergency Operation Mode
1
Trouble occurs (Display the trouble code root and trouble code on the remote control).
2
Carry out trouble reset with the remote control.
3
If the trouble indicted in
a
retry operation.
If the trouble indicated in
restart operation after carrying out the previous trouble reset (without entering the emergency operation mode).
4
If the same trouble is detected again during the retry operation in
with the remote control, then try emergency operation starting corresponding to the contents of the trouble.
Table Emergency Operation Mode Patterns and Trouble Codes for which Emergency Operation is Possible or Impossible
Emergency Mode
Codes for which emergency operation is
Pattern
possible.
When a No. 1
Serial transmission trouble
Compressor Failure
VDC sensor/circuit trouble
Bus voltage trouble
Occurs
Radiator panel overheat
protection
Overload protection
IPM Alarm output/
Bus voltage trouble/
Over Current Protection
Cooling fan trouble
Thermal sensor trouble
(Radiator panel)
IAC sensor/circuit trouble
When No. 2
Overcurrent protection
Compressor Failure
Occurs
Constant capacity
Error codes other than those at right.
unit
Error (stop)
Caution
During emergency operation, only
In case, more than
marked percentage of indoor units are operated, over than the percentage of indoor units
would be on the stand-by mode.
Failed Compressor
No.1
No.2
No. 3
1
above is of the kind that permits emergency operation (see the table below), initiate
1
above is of the kind where emergency operation is impossible (see the table below),
marked percentage of indoor units can be operated during emergency operation.
External temp. (TH6)
TH6
20˚C (cooling) or heating
TH6 < 20˚C (cooling)
TH6
20˚C (cooling) or heating
TH6 < 20˚C (cooling)
Don't care
3
above, carry out trouble reset once more
Trouble Codes for which
Emergency Operation is
Impossible
0403
Trouble codes other than
4200
those at left.
4220
4230
4240
4250
4260
5110
5301
(a)High pressure/ low-
pressure pressure
error
1302
(b)Reverse phase error
4103
(c)Communication error
No communication with
variable capacity unit
(d)Constant capacity unit
power-off and LEV2
open
(e)Oil equalization circuit
irregularity
1559
Model 600 ~ 750
60 ~ 70 %
No.2 + No.3 Compressors on
45 ~ 55 %
No.2 Compressor only
65 ~ 75 %
No.1 + No.3 Compressors on
45 ~ 55 %
No.1 Compressor only
80 ~ 90 %
No.1 + No.2 Compressors on
-88-
Action
Emergency Operation with the
No. 2 and No. 3 Compressor
* After the retry operation, even if
there is a different trouble code
detected within <Inverter
Trouble> at left, press the button
and after resetting, start the unit
by emergency operation.
[Example]
4250
Reset
Retry
Reset
Emergency
operation
Emergency Operation with the
No. 1 and No. 3 Compressor
Emergency response operation
with the variable capacity unit only
(No. 1 and No. 2 compressor).
Notes
4240