(3) Group registration of indoor unit
1)
Registration method
• Group registration of indoor unit ........................................................................ 1
The indoor unit to be controlled by a remote controller is registered on the remote controller.
[Registration procedure]
1
With the remote controller under stopping or at the display of "HO", continuously press the
A B
(
+
) at the same time for 2 seconds to change to the registration mode. (See the figure below.)
2
Assign the indoor unit address to "INDOOR UNIT ADDRESS NO." by operating the
C
adjustment) (
).
Then press the
TEST RUN
to 001.
3
After completing the registration, press the
change to the original ordinary mode (with the remote controller under stopping).
Ordinary mode
• Remote controller under stopping
˚C
INDOOR UNIT
ERROR CODE
ADDRESS NO
OA UNIT ADDRESS NO
Group setting mode
˚C
ERROR CODE
OA UNIT ADDRESS NO
TEMP
CLOCK
ON OFF
PAR-F27MEA
TIMER SET
2
Assign the
C
address ( )
System example
Remote controller
D
switch (
) to register. In the figure below, the "INDOOR UNIT ADDRESS NO." is being set
FILTER
1
1
ON/OFF
FILTER
CHECK TEST
1
3
Change to the
Press the
registration
registration
A
B
mode (
)
switch ( )
+
Indoor units
Group
A
+
+
switch (
• "HO" under displaying
˚C
INDOOR UNIT
ERROR CODE
ADDRESS NO
OA UNIT ADDRESS NO
• Registration complete
Indicates the type of unit
(Indoor unit in this case)
2 3
+
• Registration error
"88" flickers indicating registra-
tion error. (when the indoor unit
registered is not existing)
• Confirm the indoor unit address No.
• Confirm the connection of the transmission line.
D
-51-
+
FILTER
(Room temperature
B
) at the same time for 2 seconds to
˚C
ERROR CODE
OA UNIT ADDRESS NO
˚C
ERROR CODE
OA UNIT ADDRESS NO