Deleting (Clearing) an Event
Fixed events can be deleted from the time switch. If you need to delete an event, follow this procedure.
1.
If necessary, press MODE to scroll through the different mode selections until SET FIXED ON/OFF EVENTS appear on the
display.
2.
Press ENTER/NEXT as necessary to scroll through the scheduled events until you see the event you want to delete.
Press + and – at the same time until the display shows --:-- --. This indicates the event is erased.
3.
4.
If necessary, press ENTER/NEXT to advance through the other configured events.
5.
Press MODE to save the changes and exit.
Clearing Time Switch Memory
During a "Clear Time Switch Memory" operation, the time switch resets all programmed settings to their factory default value. The
following occurs:
After a brief period of time the time switch model number appears, followed by the USB Boot Loader version, EE Boot Loader
version, the firmware revision and finally the Reset Reason Code.
MEMCLR is displayed followed by DONE when the operation is completed.
To perform a "Clear Time Switch Memory" operation do the following:
1.
Press and hold ENTER/NEXT.
2.
While pressing and holding ENTER/NEXT, press and release the RESET (round) button. Do not release ENTER/NEXT.
3.
Continue to press and hold ENTER/NEXT until MEM CLEAR then DONE briefly appears.
4.
IND will now show on the display. Refer to the "Setting Output Configuration" section in these instructions.
Writing Time Switch Program Data to a USB Memory Stick
The time switch has the capability to copy its programmed data (event schedules, holidays, output configuration, DST on/off setting,
DST rule setting and geographical location) to a USB memory stick. Follow these steps to transfer all programming from the time
switch to a USB memory stick:
1.
Press MODE to advance until wr USb is displayed.
2.
Press ENTER and insUSb is displayed.
3.
Insert a USB memory stick into the USB port on the front face of the time switch.
4.
SCHEdL 01 is displayed. Press + or - to increment/decrement the schedule number on the display (01-99).
5.
When the desired number is displayed, press ENTER and this will write the data file to the USB memory stick. The file name will
be SCHEDLxx.TXT where xx is the schedule number selected in the previous step.
6.
After the file is written REMOVE is shown on the display.
7.
Remove the USB memory stick and the time switch will advance to the next mode selection. If all procedures are completed,
press MODE repeatedly until back to the operating mode selection (AUTO, ENERGY SAVER, MANUAL).
Reading Time Switch Program Data from a USB Memory Stick
The time switch has the capability to read program data (event schedules, holidays, output configuration, DST on/off setting, DST
rule setting and geographical location) from a USB memory stick. Follow these steps to transfer all programming from a USB
memory stick to the time switch:
1.
Press MODE to advance until rd USb is displayed.
2.
Insert a USB memory stick containing the desired data file into the USB port on the front face of the time switch.
3.
Press ENTER and insUSb is briefly displayed.
4.
SCHEdL.xx is displayed where xx is the first data file number found on the USB memory stick.
5.
Press + or - to scroll through the data files on the USB memory stick (if more than one file is stored on this stick).
6.
When the desired number is displayed, press ENTER and the time switch will read the data file from the USB memory stick.
7.
After the file is read into the time switch, DONE is briefly shown on the display followed by REMOVE.
8.
Remove the USB memory stick and the time switch will advance to the next mode selection. If all procedures are completed,
press MODE repeatedly until back to the operating mode selection (AUTO, ENERGY SAVER, MANUAL).