7) Remote controller custom code
(Only for wireless remote controller)
The indoor unit custom code can be changed. Select the appropriate custom code.
Function number
44
8) External input control
"Operation/Stop" mode or "Forced stop" mode can be selected.
Function number
46
9) Room temperature sensor switching (Aux.)
To use the temperature sensor on the wired remote controller only, change the setting to "Wired re-
mote controller" (01).
This function will only work if the function setting 42 is set at "Both" (01).
When the setting value is set to "Both" (00), more suitable control of the room temperature is possi-
ble by setting function setting 30 and 31 too.
Function number
48
10) Indoor unit fan control for energy saving for cooling
Enables or disables the power-saving function by controlling the indoor unit fan rotation when the
outdoor unit is stopped during cooling operation.
Function number
49
00: When the outdoor unit is stopped, the indoor unit fan operates continuously following the setting
on the remote controller.
01: When the outdoor unit is stopped, the indoor unit fan operates intermittently at a very low speed.
02: Enable or disable this function by remote controller setting.
NOTES:
• As the factory setting, this setting is initially activated.
• Set to "00" or "01" when connecting a remote controller that cannot set the Fan control for ener-
gy saving function or connecting a network converter.
To confirm if the remote controller has this setting, refer to the operating manual of each remote
controller.
11-1. Function settings by using remote controller
Setting value
00
01
02
03
Setting value
00
01
02
03
Setting value
00
01
Setting value
00
01
02
- 34 -
Setting description
A
B
C
D
Setting description
Operation/Stop mode 1
(Setting prohibited)
Forced stop mode
Operation/Stop mode 2
Setting description
Both
Wired remote controller
Setting description
Disable
Enable
Remote controller
Factory setting
Factory setting
Factory setting
Factory setting
11. Function settings