4.1

GENERAL

The Print keys provide access to two sets of informa-
tion either locally on the panel display or, if an optional
printer is connected, remotely as hard copy printouts.
The Operating Data (Oper Data) key provides a real-time
list of system operating data and programmed settings.
The History key provides a comprehensive list of op-
erating data and programmed settings "at the instant of
fault" on each of the last six faults (local display) or three
faults (remote printout) which occurred on the chiller.
4.2

OPER DATA KEY

If a remote printer is not connected, pressing the Operat-
ing Data key allows the user to scroll through informa-
tion, on the 40 character display, which is not directly
available from the Display keys on the panel.
If a remote printer is connected, pressing the Operating
Data key causes a snapshot to be taken of system oper-
ating conditions and of the user programming selections.
The data is stored in temporary memory, then transmitted
from the microprocessor to the remote printer. As the
data is transmitted it is erased from the memory.
JOHNSON CONTROLS

4. PRINT KEYS

Information available using the Operating Data key is
described in the following sections. In example displays "
# " is used to indicate system number where appropriate.
4.3
OPERATING DATA –
LOCAL DISPLAY MESSAGES
YCAS 2 SYSTEM MODELS :
When the Operating Data key is pressed, the following
message appears:
O P E R A T I N G
Repetitively pressing the keys will scroll through
the following Common (whole chiller) Data and indi-
vidual System Data information displays.
Common Data:
L O A D
U N L O A D
This message shows the time remaining on the Load
Timer and the Unload Timer. These Timers constantly
recycle and are used in conjunction with "rate control"
and "temperature deviation from setpoint" to determine
when loading should occur.
FORM 201.18-NM7
29023A
D A T A
D I S P L A Y S
T I M E R
1 0
T I M E R
0
8
S E C
S E C
147