Temperature And Flows - York YCAS0098EB Installation Operation & Maintenance

Air-cooled liquid chillers
Hide thumbs Also See for YCAS0098EB:
Table of Contents

Advertisement

Technical Data
MODEL
NUMBER
YCAS
MIN.
0098
0118
0128
0138
0148
0158
0178
0198
0208
NOTES:
1. For leaving brine temperature below 40°F, contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 5.5°F, contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freeze-up to -20°F with an electrical heater as standard.
MODEL
NUMBER
YCAS
MIN.
0098
0118
0128
0138
0148
0158
0178
0198
0208
NOTES:
1. For leaving brine temperature below 5°C, contact your nearest YORK office for application requirements.
2. For leaving water temperature higher than 13°C, contact the nearest YORK office for application guidelines.
3. The evaporator is protected against freeze-up to -28.8°C with an electrical heater as standard.
JOHNSON CONTROLS

TEMPERATURE AND FLOWS

(ENGLISH UNITS)
LEAVING WATER
TEMPERATURE (°F)
MAX
1
.2
40
55
40
55
40
55
40
55
40
55
40
55
40
55
40
55
40
55
Excessive flow, above the max GPM,
will damage the evaporator.
TEMPERATURE AND FLOWS
LEAVING WATER
TEMPERATURE (°C)
MAX.
1
2
4.4
12.8
4.4
12.8
4.4
12.8
4.4
12.8
4.4
12.8
4.4
12.8
4.4
12.8
4.4
12.8
4.4
12.8
COOLER FLOW
(GPM)
3
MIN.
MAX.
141
403
141
403
180
768
141
403
180
768
180
768
180
768
180
768
180
768
(SI UNITS)
COOLER FLOW
(L/S)
3
MIN.
MAX.
8.9
25.4
8.9
25.4
11.3
48.5
8.9
25.4
11.3
48.5
11.3
48.5
11.3
48.5
11.3
48.5
11.3
48.5
FORM 201.18-NM7
AIR ON
CONDENSER (°F)
MIN.
MAX
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
0
125
AIR ON
CONDENSER (°C)
MIN.
MAX
-17.7
50
-17.7
50
-17.7
50
-17.7
50
-17.7
50
-17.7
50
-17.7
50
-17.7
50
-17.7
50
47