Print Keys; General; Oper Data Key; Operating Data - Local Display Messages - York YCAS Series Installation Operation & Maintenance

Air-cooled screw liquid chillers
Hide thumbs Also See for YCAS Series:
Table of Contents

Advertisement

Micro Panel Contents
4.1

GENERAL

The Print keys provide access to two sets of informa-
tion either locally on the panel display or, if an optional
printer is connected, remotely as hard copy printouts.
The Operating Data (Oper Data) key provides a real-
time list of system operating data and programmed set-
tings. The History key provides a comprehensive list
of operating data and programmed settings "at the in-
stant of fault" on each of the last six faults (local dis-
play) or three faults (remote printout) which occurred
on the chiller.
4.2

OPER DATA KEY

If a remote printer is not connected, pressing the Oper-
ating Data key allows the user to scroll through infor-
mation, on the 40 character display, which is not di-
rectly available from the Display keys on the panel.
If a remote printer is connected, pressing the Operating
Data key causes a snapshot to be taken of system oper-
ating conditions and of the user programming selec-
tions. The data is stored in temporary memory, then
transmitted from the microprocessor to the remote
printer. As the data is transmitted it is erased from the
memory.
128

4. PRINT KEYS

Information available using the Operating Data key is de-
scribed in the following sections. In example displays " # "
is used to indicate system number where appropriate.
4.3
OPERATING DATA –
LOCAL DISPLAY MESSAGES
YCAS 2 SYSTEM MODELS :
When the Operating Data key is pressed, the following
message appears:
O P E R A T I N G
Repetitively pressing the áâkeys will scroll through
the following Common (whole chiller) Data and indi-
vidual System Data information displays.
Common Data:
L O A D
U N L O A D
This message shows the time remaining on the Load
Timer and the Unload Timer. These Timers constantly
recycle and are used in conjunction with "rate control"
and "temperature deviation from setpoint" to determine
when loading should occur.
FORM 201.18-NM1 (102)
29023A
D A T A
D I S P L A Y S
T I M E R
1 0
T I M E R
0
YORK INTERNATIONAL
S E C
S E C