Group -Pid Parameters - HNC HV10 Series User Manual

Table of Contents

Advertisement

UP/DOWN terminal modification rate
02.27
0.0Hz~99.9Hz/s
The function code is the frequency modification rate when setting the UP/DOWN terminal as frequency set , that is, the UP/DOWN terminal is short-circuited with the
GND terminal for 1s, and the frequency changes.
Input terminal pulse trigger mode setting (DI1~DI5)
02.28
0~1FH
0: indicates the electrical level trigger mode
1: indicates the pulse trigger mode
Note:
DI1~DI5 correspond to 1H, 2H, 4H, 8H and 10H in hexadecimal.
Input terminal valid logic setting (DI1~DI5)
02.29
0~1FH
0: indicates positive logic, that is, the DI terminal is connected to GND and GND is valid, and the disconnection is invalid
1: It means anti-logic, that is, DI terminal is not connected to the GND terminal and GND is invalid, and the disconnection is valid
Note:
DI1~DI5 correspond to 1H, 2H, 4H, 8H and 10H in hexadecimal.
DI1 filter coefficient
02.30
0~9999
DI2 filter coefficient
02.31
0~9999
DI3 filter coefficient
02.32
0~9999
DI4 filter coefficient
02.33
0~9999
DI5filter coefficient
02.34
0~9999
Used to set the sensitivity of the input terminal. If the digital input terminal is susceptible to interference and causes misoperation, this parameter can be increased
to enhance the anti-interference ability, but the sensitivity of the input terminal will be reduced if the setting is too large.
1: represents 2ms scanning time unit

03 group -PID parameters

PID function setting
03.00
0000~2122
Figure 02-6 Schematic diagram of frequency level detection
49
1.0
0
0
5
5
5
5
5
1010