User password
00.23
0~9999
The user password setting function is used to prohibit unauthorized personnel from viewing and modifying function parameters.
When setting the user password, enter any non-zero number, press the key
When you need to change the password, select the 00.23 function code and press the key
verification is successful, enter the modification state, enter the new password, and press the key
password will automatically take effect after 3 minutes.
Please keep the password properly. If you forget it, please ask the manufacturer for service.
Frequency display resolution selection
00.24
0~1
0:0.1 Hz(0.0~999.9 HZ)
1:1 Hz(0~999 HZ)
Group 01-auxiliary operating parameters
Starting method
01.00
00~12
LED units: start mode
0: Start from the starting frequency
Start according to the set starting frequency (01.01).
1: DC braking + starting frequency start
Perform DC braking first (see 01.03), and then start according to mode 0.
2: reserved
LED ten digits: restart mode after power failure or abnormal
0: invalid
When the power is turned on after a power failure, the inverter will not run automatically.
1: Start from the starting frequency
When the power is turned on after a power failure, if the starting conditions are met, the inverter will automatically start to run from the starting frequency point.
Starting frequency
01.01
0.00~50.00Hz
The starting frequency refers to the initial frequency when the inverter starts. For some systems with relatively large starting torque, setting a reasonable starting
frequency can effectively overcome the problem of starting difficulties.
Starting DC braking current
01.02
0.0~150.0%*Motor rated current
Start DC braking time
01.03
0.0~100.0s
The setting of starting DC braking current is the percentage relative to the rated output current of the inverter.
When the starting DC braking time is 0.0s, there is no DC braking process. The details are shown in the figure below.
to confirm, and the password will automatically take effect after 3 minutes.
E N T E R
to enter the password verification state. After the password
E N T E R
to confirm, the password change is successful, and the
E N T E R
36
0
0
00
1.00
0.0%