Adjusting The Burner; Instructing The System User; Operating And Service Documents - Viessmann Vitoplex 100 Service Instructions For Contractors

Oil/gas boiler
Table of Contents

Advertisement

Checking the Vitoair draught stabiliser (if installed)
Release the latch on the control disc.

Adjusting the burner

Burner service instructions or separate docu-
mentation from the burner manufacturer
Adjust the maximum oil or gas throughput of the
burner to the rated boiler heating output.
Rated heating
Pressure drop on the hot gas
output
side
kW
Pa
150
200
250
310
400
410
500
620

Instructing the system user

The installer should instruct the user in the operation of
the system.

Operating and service documents

1. Complete and detach the customer registration
card:
Hand the system user their section for safekeep-
ing.
Retain the heating contractor's section.
mbar
60
0.6
120
1.2
130
1.3
230
2.3
250
2.5
250
2.5
230
2.3
310
3.1
Commissioning, inspection, maintenance
The control disc must swing freely during burner oper-
ation.
The minimum boiler water temperature for oil and gas
operation is 75 °C.
Ensure a (minimum) boiler return temperature of
65 °C.
Set the minimum heating output for the base load
stage according to the conditions of the flue system.
Note that the flue system must be suitable for the low
flue gas temperatures that may occur.
In the event of frequent cycling in standby mode and
for partial loads below 40 %, we recommend the fol-
lowing:
Insulate the flue gas collector.
Install a motorised flue gas damper.
Set the minimum boiler runtime to 10 min.
This extends the service life and reduces running
costs.
2. File all parts lists, operating and service instruc-
tions in the folder and hand this over to the system
user.