Faults indicated in the "Faults" menu

Flow temp.
System too slow
Outside temp.
Frost prot. flow
Cause:
Flow temperature sensor
not/incorrectly connected or faulty
Result:
Functions based on the flow
temperature are failing
Remedy:
Check the connections and the
sensor using the resistance table
(see page 34)
Cause:
The flow temperature does not reach
the set value less the set temperature
difference within the set period
Result:
The control unit stays in use as
normal
Remedy:
Check system components. If
necessary, match the set time and/or
temperature difference.
Reset the fault by pressing
Cause:
Outside temperature sensor
not/incorrectly connected or faulty
Result:
The control unit changes over to
average outside temperature.
Some functions based on the
outside temperature are failing.
Remedy:
Check the connections and the
sensor using the resistance table
(see page 34)
Cause:
The flow temperature is too low to
ensure frost protection
Result:
The control unit creates a heat
demand. The set flow temperature is
raised for frost protection at least to
the set value.
Remedy:
Check system components
Troubleshooting
twice.