Separate Power Supply - Viessmann EM-EA1 Installation And Service Instructions For Contractors

Dio electronics module function extension
Table of Contents

Advertisement

Power supply
Power supply at heat generator
A
L
N
N
L
?
?
N
L
156
Fig. 10
Extension (electronics module)
A
Power supply
A Power supply for further accessories
Plug for heat generator accessories power supply
aBH

Separate power supply

If the power supply for the extension is not made at
the heat generator.
Danger
Incorrect electrical installations can lead to seri-
ous injury from electrical current and result in
appliance damage.
Connect the power supply and implement all
safety measures (e.g. RCD circuit) in accord-
ance with the following regulations:
IEC 60364-4-41
VDE regulations
TAR medium voltage VDE-AR-N-4110
Danger
The absence of system component earthing can
lead to serious injury from electric current if an
electrical fault occurs.
The appliance and pipework must be connected
to the equipotential bonding of the building.
Create the power supply connection.
Route the power cable to the heat generator and con-
nect to plug
. Observe MCB/fuse protection, out-
aBH
put, plug
of the heat generator.
aBH
If power is supplied to a further accessory, use
plug
A provided
Heat generator installation and service instruc-
tions
Danger
Incorrect core assignment can result in serious
injury and damage to the appliance.
Never interchange cores "L" and "N".
Isolators for non-earthed conductors
The mains isolator (if installed) must simultaneously
isolate all non-earthed conductors from the mains
with a minimum contact separation of 3 mm.
If no mains isolator is installed, all non-earthed con-
ductors must be isolated from the power supply by
the upstream circuit breaker with a minimum contact
separation of 3 mm.
7