A.O. Smith DSE-5 Instruction Manual page 11

Commercial electric water h
Table of Contents

Advertisement

Not More Than Three Conductors in Raceway or Cable or Earth (Directly Buried), Based on Ambient Temperature of 30°C (86°F)
Size
60°C
(140°F)
TYPES
AWG
RUW, T
TW, UF
MCM
18
......
16
......
14
15
12
20
10
30
8
40
6
55
4
70
3
80
2
1
0
00
000
0000
250
300
350
400
500
Ambient
For ambient temperatures over 30°C, multiply the ampacities shown by the appropriate correction factor to determine the maximum
Temperature
allowable load current.
°C
31-40
.82
41-50
.58
51-60
......
61-70
......
71-80
......
= The load current rating and the overcurrent protection for these conductors shall not exceed 15 amperes for 14 AWG, 20 amperes for 12 AWG, and 30 amperes for 10
AWG copper; or 15 amperes for 12 AWG and 25 amperes for 10 AWG aluminum and copper-clad aluminum.
Immersion
standard
number of 50a contractors
heaters***
kw
no. of
ratings
208V
wattage
3
1
3,000
6
1
6,000
1
9
1
9,000
12
1
12,000
15
1
15,000
18*
1
18,000
24
2
12,000
2
30
2
15,000
36*
2
18,000
45
3
15,000
3
54
3
18,000
60**
4
15,000
4
75**
5
18,000
5
90**
5
18,000
* 208V models use one additional immersion heater.
** Available on 50 gallon models or larger.
*** Each immersion heater contains three electric elements.
Allowable Ampacities of Insulated Conductors
Temperature Rating of Conductor
75°C
85°C
(167°F)
(185°F)
TYPES
FEPW
RH, RHW
RUH,
TYPES
SIS, =FEP,
THW,
V, MI
THWN,
XHHW
USE, ZW
=XHHW*
COPPER
......
......
......
22
15
25
20
30
30
40
45
50
65
70
85
90
100
105
115
120
130
140
150
155
175
185
200
210
230
235
255
270
285
300
310
325
335
360
380
405
CORRECTION FACTORS
.88
.90
.75
.80
.58
.67
.35
.52
......
.30
standard kw Inputs
240V
480V
1
1
2
3
2
4
5
3
taBle 1.
90°C
60°C
(194°F)
(140°F)
(167°F)
TYPES
TYPES
TA, TBS
RH, RHW
SA, AVB
TYPES
RUW, T
THW,
=FEPB,
TW, UF
THWN
=RHH,
XHHW,
=THHN,
ALUMINUM OR COPPER-CLAD ALUMINUM
21
......
22
......
25
......
30
15
40
25
50
30
70
40
90
55
105
65
120
75
140
155
185
210
235
270
300
325
360
405
.91
.82
.82
.58
.71
......
.58
......
.41
......
taBle 2.
full load current In amperes
single phase
208V
240V
277V
14.4
12.5
10.8
28.8
25.0
21.2
43.3
37.5
32.5
57.7
50.0
43.3
72.1
62.5
54.2
86.5
75.0
65.0
115.4
100.0
86.6
144.2
125.0
108.3
173.1
150.0
130.0
216.3
187.5
162.5
N/A
225.0
194.9
N/A
250.0
216.6
N/A
N/A
N/A
N/A
N/A
N/A
11
75°C
85°C
90°C
(185°F)
(194°F)
TYPES
TA, TBS,
RUH
SA, AVB
TYPES
SIS,
V, MI
=RHH,
=THHN,
USE
=XHHW*
......
......
......
......
......
......
......
......
......
15
25
25
25
30
30
40
40
40
50
55
55
65
70
70
75
80
80
90
95
95
100
110
110
120
125
125
135
145
145
155
165
165
180
185
185
205
215
215
230
240
240
250
260
260
270
290
290
310
330
330
.88
.90
.91
.75
.80
.82
.58
.67
.71
.35
.52
.58
......
.30
.41
three phase
480V
208V
6.3
8.3
12.5
16.7
18.8
25.0
25.0
33.3
31.3
41.6
37.5
50.0
50.0
66.6
62.5
83.3
75.0
99.9
93.8
124.9
112.5
149.9
125
166.7
156
208.4
188
250
Size
AWG
MCM
......
......
......
12
10
8
6
4
3
2
1
0
00
000
0000
250
300
350
400
500
Ambient
Temperature
°F
86 –104
105–122
123–141
142–158
159–176
240V
480V
7.2
3.6
14.4
7.2
21.7
10.8
28.9
14.4
36.1
18.0
43.3
21.7
57.7
28.9
72.2
36.1
86.6
43.3
108.3
54.1
129.9
65.0
145
72
181
90
217
108