Troubleshooting; Specification - Philips Dynalite DRC810DT Installation Manual

Spdt dry contact relay controller
Table of Contents

Advertisement

Check the following list. If you are still unable to rectify the situation, contact your nearest Dynalite dealer. A
complete list of distributors worldwide can be found on the Internet at:
Please ensure that you have completed the following prior to calling our technical support department.
Check all symptoms in the Troubleshooting list
Check for any deviations between the installation and the installation instructions
Make a list of the model numbers of all devices used in the system
SYMPTOM
Load Controller does not operate at all. No Service
LED activity. Power supply indicator LED on PCB
not lit.
Power supply indicator LED lit, but no Service LED
activity.
Load Controller will not respond to control panel
push buttons.
Load Controller operates properly but circuit
breakers keep tripping.
Fluorescent lights won't dim.
Maximum Total Box Load:
Switching Device:
Control Inputs:
User Controls:
Internal Controls:
DyNet DC Supply +VE:
Preset Scenes:
Supply Terminals:
Output Terminals:
Cable Entries:
Diagnostic Functions:
Compliance:
Construction:
Dimensions:
PROBABLE CAUSE
Incorrect connection of Mains supply, or no
power available.
Supply voltage too low, short circuit on
network. Control PCB faulty.
Control panel incorrectly wired or incorrect
configuration.
Instant tripping: - short circuit on load.
Delayed tripping: - Load Controller overloaded.
Wrong type of ballast or ballast incorrectly
wired. Control cable from DRC810DT to
ballasts not installed.
Supply:
230V ±14% 50/60Hz Single Phase at 0.1A
8 x SPDT voltage free changeover contacts rated at 10 Amps resistive
Outputs:
80A
Relay - NO contact: 10A resistive TV8 rated, NC contact: 10A resistive TV3 rated
1 x RS485 DyNet/DMX512 serial port
1 x programmable dry contact AUX input
8 x multifunction dry contact or analogue inputs
Service Switch
Diagnostic LED
Programmable Logic Controller
Dynalite Accessory Module enabled
120mA (supply for approx. 6 Panels)
170
Line, Neutral – 1 x 4mm
C, NO, NC for each channel
2
1 x 2.5mm
max conductor size
Earth link bar provided
Mains – 1 x 75mm x 53mm removable gland plate
Data – 1 x 25mm dia. knockout
Device Online/Offline status
Circuit run time tracking (optional)
CE, C-Tick
Alloy/Steel wall mount case with epoxy finish
Height 320mm x Width 225mm x Depth 75mm (excludes wall brackets)
Weight:
3.5 Kilograms
www.philips.com/dynalite
ACTION
Check power supply to Load Controller. Check
Line and Neutral input connections.
Check supply voltage is at least 75% of rated
voltage. Check 5V & 12V terminal voltages, 5V
supply must be present. Disconnect network bus
and restore power. Replace control PCB.
Check operation of LEDs on control panel. Push
button on panel and study response of service
LED.
Check load wiring for short circuits.
Verify Load Controller loading with current tester
(don't forget to de-rate for low power-factor loads
and transformer losses). Check that the breaker
terminals are tight.
Check ballast type. Check actual wiring against
ballast manufacturer's diagram. Check 1-10V/DSI
cable and settings.
product specifications
2
max conductor size
DRC810DT Installation Manual Rev I.docx

troubleshooting

9