External Output - Fujitsu ASYG12KMCDN Design & Technical Manual

Wall mounted type
Table of Contents

Advertisement

8-2. External output

Use an external output cable with appropriate external dimension, depending on the number of ca-
bles to be installed.
¢ External input and output PCB
• A twisted pair cable (22AWG) should be used. Maximum length of cable is 25 m.
• Output voltage: High DC 12 V±2 V, Low 0 V.
• Permissible current: 50 mA
• For details, refer to
• When indicator or other components are connected directly:
Example: Rotary SW on External input and output PCB is set to "1".
(Operation status)
(Indoor unit fan
operation status)
• When connecting with a device equipped with a power supply:
Example: Rotary SW on External input and output PCB is set to "1".
Connected device 1
Connected device 2
Connected device 3
8-2. External output
"Combination of external input and output"
Connected unit
Resistor
LED 1
Resistor
LED 2
(Error status)
Resistor
LED 3
Connected unit
(Operation status)
(Error status)
(Indoor unit fan
operation status)
on page 20.
Relay
- 19 -
PCB
+