To Hook The Unit On The Mounting Plate; To Pass The Pipes Through The Wall Hole; To Provide Drainage - Daikin FAA-B Installation And Operation Manual

Split system air conditioner
Table of Contents

Advertisement

b
a
a
Cut off for side piping
b
Cut off for bottom piping
1 Remove the front grille.
2 Cut off the pipe port cover from inside the front grille using a
coping saw.
3 Remove any burrs along the cut section using a half round
needle file.
NOTICE
Do NOT use nippers to remove the pipe port cover, as this
would damage the front grille.
12.2.4

To hook the unit on the mounting plate

1 Remove the front panel.
2 Set the indoor unit on the mounting plate hooks. Use the " "
marks as a guide.
3 Place piece of packing material for support.
a
b
c
d
e
a
Front grille
b
Refrigerant piping
c
Tab 2×
d
Mounting plate (accessory)
e
Piece of packing material
12.2.5

To pass the pipes through the wall hole

1 Connect the drain piping
"12.2.6  To provide
the refrigerant piping
"13  Piping
electrical wiring
"14 Electrical
FAA71+100BUV1B
Split system air conditioner
3P654518-1A – 2021.03
drainage"  [ 4   15],
installation"  [ 4   16] and the
installation" [ 4  17].
2 Shape the refrigerant pipes along the pipe path marking on the
mounting plate.
3 Fix the electrical wiring and the refrigerant pipes together using
vinyl tape (field supply).
a
b
d
c
e
a
Drain hose
b
Wall hole
c
Refrigerant piping
d
Electrical wiring
e
Vinyl tape (field supply)
f
Power supply wiring
g
Transmission wiring and user interface wiring
NOTICE
▪ Do NOT bend refrigerant pipes.
▪ Do NOT push the refrigerant pipes onto the bottom
frame or the front grille.
4 Pass the drain hose and refrigerant pipes through the wall hole.
5 When the complete installation is finished (drain piping
drainage"  [ 4   15], the refrigerant piping
"12.2.6  To provide
installation"  [ 4   16] and the electrical wiring
"13  Piping
installation"  [ 4   17]), fix the indoor unit on the
"14  Electrical
mounting plate
"15.1  To fix the unit on the mounting
plate" [ 4  19].
12.2.6

To provide drainage

INFORMATION
Make sure to check and follow the General guidelines for
draining in the installer reference guide of the indoor unit.
To connect the piping on right side, right-back, or
right-bottom
INFORMATION
The factory default is right-side piping. For left-side piping,
remove the piping from the right side and install it on the
left side.
1 Attach the drain hose with adhesive vinyl tape to the bottom of
the refrigerant pipes.
2 Wrap the drain hose and the refrigerant pipes together using
insulation tape.
12 Unit installation
A
A
f
c
g
Installation and operation manual