Installation Instruction; Select The Best Location; Indoor/Outdoor Unit Installation Diagram - Panasonic CS-S18HKQ Service Manual

Indoor unit outdoor unit
Table of Contents

Advertisement

11 Installation Instruction

11.1. Select The Best Location

INDOOR UNIT
• There should not be any heat source or steam near the unit.
• There should not be any obstacles blocking the air
circulation.
• A place where air circulation in the room is good.
• A place where drainage can be easily done.
• A place where noise prevention is taken into consideration.
• Do not install the unit near the door way.
• Ensure the spaces indicated by arrows from the wall, ceiling,
fence or other obstacles.
• Recommended installation height for indoor unit shall be at
least 2.5 m.
OUTDOOR UNIT
• If an awning is built over the unit to prevent direct sunlight or
rain, be careful that heat radiation from the condenser is not
obstructed.
• There should not be any animal or plant which could be
affected by hot air discharged.
• Keep the spaces indicated by arrows from wall, ceiling,
fence or other obstacles.
• Do not place any obstacles which may cause a short circuit
of the discharged air.
• If piping length is over 10.0 m, additional refrigerant should
be added as shown in the table.
Rated
Piping size
Length
Model
(m)
Gas Liquid
S18HKQ 1/2"
1/4"
5
S24HKQ 5/8"
1/4"
5
Example: For S24HKQ
If the unit is installed at 15 m distance, the quantity of additional
refrigerant should be 100 g.... (15-10) m x 20 g/m = 100 g.
Max
Min.
Max.
Additional
Elevation
Piping
Piping
Refrigerant
(m)
Length
Length
(m)
(m)
20
15
3
3
20
15
11.2. Indoor/Outdoor Unit
Installation Diagram
(g/m)
15
20
24