Commissioning, inspection, maintenance
Further details regarding the individual steps
Checking the domestic ventilation system
Danger
The simultaneous operation of
open flue combustion equipment
(e.g. an open fireplace) and the
Vitovent in a space where the
combustion air supply is intercon-
nected results in dangerous neg-
ative pressure inside the room.
The negative pressure can result
in a return of flue gases into the
room interior.
■ Never operate the Vitovent
simultaneously with open flue
combustion equipment (e.g.
open fireplace).
■ Only operate solid fuel com-
bustion equipment in bal-
anced flue mode with its inde-
pendent outdoor air and
exhaust air duct.
■ Doors to heating rooms where
the combustion air supply is not
interconnected with the living
space must be airtight and
must be kept shut.
6
Information regarding the operation
of the Vitovent 300 in conjunction
with open flue combustion equipment
■ Always install an interlock system on
site. In case of negative pressure
inside the room, the interlock system
(e.g. air pressure limiter "P4" made by
Erich Huber, www.luftdruck-
waechter.de) must switch off the
Vitovent.
■ The relevant flue gas inspector must
give his approval [check local regula-
tions].
■ The frost protection must be disabled
(remote control) and frost protection
must be ensured through an electric
preheater bank (accessory) or a geo-
thermal heat exchanger (on-site).
!
Please note
The simultaneous operation of
extractor hoods or tumble dryers
and the Vitovent in interconnec-
ted rooms results in negative
pressure inside the room.
■ Never link extractor hoods and
tumble dryers into the Vitovent
duct system.
■ Set up extractor hoods in the
kitchen either to recirculate air
or to expel the air to the out-
side.
Recommendation: Recirculat-
ing extractors offer a better
energy balance.