Table 2 Electrical Specifications - Bard Q24A2DA Installation Instructions Manual

Packaged air conditioner
Table of Contents

Advertisement

No.
Rated
Field
MODEL
Volts &
Power
Phase
Circuits
Q24A2DA0Z
1
A05
230/208-1
1
A10
1
Q24A2DB0Z
1
B06
230/208-3
1
B09
1
Q24A2DC0Z
1
C06
460-3
1
C09
1
Q30A2DA0Z
1
A05
230/208-1
1
A10
1
Q30A2DB0Z
1
B06
1
230/208-3
B09
1
B12
1
Q30A2DC0Z
1
C06
1
460-3
C09
1
C12
1
Q36A2DA0Z
1
A05
1
230/208-1
A10
1
A15
1 or 2
Q36A2DB0Z
1
B06
1
230/208-3
B09
1
B15
1
Q36A2DC0Z
1
C06
1
460-3
C09
1
C15
1
Q42A2DA0Z
1
A05
1
230/208-1
A10
1
A15
1 or 2
Q42A2DB0Z
1
B06
1
230/208-3
B09
1
B15
1
Q42A2DC0Z
1
C06
1
460-3
C09
1
C15
1
Q48A2DA0Z
1
A05
1
230/208-1
A10
1
A15
1 or 2
Q48A2DB0Z
1
B06
1
230/208-3
B09
1
B15
1
Q48A2DC0Z
1
C06
1
460-3
C09
1
C15
1
Q60A2DA0Z
1
A10
230/208-1
1
A15
1 or 2
Q60A2DB0Z
1
B09
230/208-3
1
B15
1
Q60A2DC0Z
1
C09
460-3
1
C15
1
j Maximum size of the time delay fuse or HACR type circuit breaker for protection of field wiring conductors.
 Based on 75°C copper wire. All wiring must conform to the National Electrical Code and all local codes.
 These "Minimum Circuit Ampacity" values are to be used for sizing the field power conductors. Refer to the National Electric
Code (latest revision), article 310 for power conductor sizing.
CAUTION: When more than one field power conductor circuit is run through one conduit, the conductors must be derated.
Pay special attention to Note 8 of Table 310 regarding Ampacity Adjustment Factors when more than three
conductors are in a raceway.
Manual 2100-602A
Page
6 of 41
TABLE 2
ELECTRICAL SPECIFICATIONS
Single Circuit
j
Maximum
Field
Minimum
External
Power
Circuit
Fuse or
Wire
Ampacity
Ckt. Brkr.
Size
22
30
10
30
30
10
55
60
6
17
20
12
25
25
10
33
35
8
10
15
14
12
15
14
17
20
12
25
35
8
32
35
8
57
60
6
18
25
10
25
25
10
34
35
8
43
45
6
11
15
14
14
15
14
18
20
12
23
25
10
29
45
8
34
45
8
58
60
6
84
90
4
21
30
10
26
30
10
35
35
8
53
60
6
12
15
14
14
15
14
18
20
12
27
30
10
35
50
8
35
50
8
58
60
6
83
90
4
26
35
8
26
35
8
35
35
8
53
60
6
13
15
14
14
15
14
18
20
12
27
30
10
37
50
8
37
50
8
58
60
6
83
90
4
28
40
8
28
40
8
35
40
8
53
60
6
14
20
12
14
20
12
18
20
12
27
30
10
45
60
8
59
60
6
84
90
4
31
45
8
36
45
8
55
60
6
16
20
12
19
20
12
28
30
10
 Minimum
j Maximum
Circuit
External Fuse
Ground
Ampacity
or Ckt. Breaker
Wire
Ckt. A
Ckt. B
Ckt. A
10
10
10
12
10
10
14
14
12
10
10
10
10
10
10
10
14
14
12
10
10
10
8
8
58
25
60
10
10
10
10
14
14
12
10
10
10
8
8
58
25
60
10
10
10
10
14
14
12
10
10
10
10
8
58
25
60
10
10
10
10
12
12
12
10
10
10
8
59
25
60
10
10
10
12
12
10
Dual Circuit
Field Power
Ground
Wire Size
Wire Size
Ckt. B
Ckt. A
Ckt. B
Ckt. A
25
6
10
10
25
6
10
10
25
8
10
10
25
8
10
10
Ckt. B
10
10
10
10