Eaton IZM97 Instruction Manual page 95

Table of Contents

Advertisement

Section 7: Wiring diagrams
PXR alarm wiring
24VDC ±10%
Control Power
ALM2
ALM3
ALM-Com
ALM1
13
15
19
14
16
20
IZM series circuit breaker
Notes:
1. For the PXR20/25, the Alarm 1 is for Remote Indication/ Maintenance Mode indication. Contact rating 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0.5 A @ 230 Vac.
2. For the PXR20/25, the Alarm 2 is for High Load alarm/Ground Fault alarm. Contact rating 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0.5 A @ 230 Vac.
3. For the PXR20/25, the Alarm 3 is for Trip N.O. contact. Contact rating 1 A @ 120 Vac, 1 A @ 24 Vdc, and 0.5 A @ 230 Vac.
4. If the control voltage is +24 Vdc, the trip unit should be fed from a separate, galvanically isolated + 24 V voltage dc supply.
New generation IZM97, 99 low voltage air circuit breaker instruction manual MN013010EN February 2020 www.eaton.com.cn
91