3.4 E7: EEPROM error
Digital display output
Description
EEPROM error.
All units stop running.
Error code is displayed on the malfunction MS box.
The indoor unit display board or wired controller connected to this MS displays "F8".
Trigger / recover condition
Trigger condition: MS EEPROM parameter is mismatch.
Recover condition: Cannot recover.
Reset method: Manually restart.
Possible causes
MS PCB damaged.
Procedure
Replace the MS main PCB
E7
V6R VRF 50Hz
153