Vacuum circuit breaker operator modules 4.16 kv to 38 kv

Advertisement

50
Table 9: Circuit breaker control data
ANSI/IEEE C37.06 control voltages
Range
Nominal
Close
24 Vdc
19-28
48 Vdc
36-56
125 Vdc
100-140
250 Vdc
200-280
120 Vac
104-127
240 Vac
208-254
Footnotes:
Current at nominal voltage
1.
Capacitor trip
2.
Value preceding slash (/) is the current for the standard trip coil with standard rating interrupting time.
3.
Value following (/) is current for optional trip coil with three-cycle interrupting time.
---- means this selection is not available at this voltage.
4.
Table 10: Interrupting capacity auxiliary switch contacts
Continuous
Type of
current
circuit
amperes
Non-
10
inductive
Inductive
10
Footnotes:
Two contacts in series.
1.
All switches are non-convertible.
2.
Close
Trip coil
coil
Trip
A
A
1
1
14-28
5.7
15/----
28-56
11.4
11.4/30
70-140
2.1
4.8/7.4
140-280
2.1
4.2/9.6
104-127
2.0
----
2
208-254
2.0
----
2
2
Control circuit voltage
120 Vac
240 Vac
10
5
6
3
Spring charging motor
Run
Inrush
(Average)
(Peak)
1
A
A
----
----
8
25
3
4
18
3
2
10
3
6
----
3
----
48 Vdc
125 Vdc
10/30
9.6
1
10
6
Charging
Seconds
----
10
10
10
10
10
250 Vdc
4.8
3

Advertisement

loading