Rinnai RHFE-951ETR Installation Manual page 13

Power flued flamefire space heater co-axial flue system
Hide thumbs Also See for RHFE-951ETR:
Table of Contents

Advertisement

4
4. Slide the external wall plate over the outer pipe protruding through the exterior wall.
symbol to point downwards which will result in a 2° fall of the horizontal section of flue pipe towards the appliance
as required.
!
Once the external wall plate is in the correct position secure it to the wall using the three 22mm screws
into the holes provided.
two horizontal holes and the two 7mm screws provided.
5.
Cut the flue pipe end protruding through the exterior wall in accordance with "CUTTING ~ ASPDFK,
ASPKIT03, ESPIPE900 & ESROOFCOWL FLUE PIPES" on page 19.
The joints between ASPDFK and ESPIPE900 and any additional ESPIPE900 lengths MUST BE
secured by a pop rivet or screw through the outer Co-ax pipes to prevent accidental or erroneous
CAUTION
dislodgement. ASPDFK components and ESPIPE900 DO NOT require cutting to be joined.
6. Now prepare the vertical section of the flue system by assembling, connecting and securing ESBEND,
ESCONDK and subsequent ESPIPE900 lengths as required in accordance with the relevant sections under
"COMPONENT ASSEMBLY & CONNECTION ~ ESBEND" refer to page 21, "COMPONENT ASSEMBLY &
CONNECTION ~ ESCONDK" refer to page 21 and "COMPONENT ASSEMBLY & CONNECTION ~
ESPIPE900" refer to page 19.
ONLY use PVC cement between externally located joints of PVC pipes to secure and seal these
joints against ingress of dust and water.
CAUTION
ONLY use non acidic silicone sealant between externally located joints of PVC flue pipes and
any mating aluminium components (such as the condensate trap) to secure and seal these joints
against ingress of dust and water. Silicone containing acetic acid, (characteristically having a
vinegar odour), as the curing agent or other acids may cause corrosion of aluminium components
and MUST NOT be used.
Secure the vertical flue sections to the wall using the clips provided to prevent accidental
dislodgement.
7. If a vertical roof terminal is used cut in accordance with"CUTTING ~ ASPDFK, ASPKIT03, ESPIPE900 &
ESROOFCOWL FLUE PIPES" on page 19 and assemble and connect in accordance with "All "External Wall",
"Internal Wall", "Sideways" and "Under Floor" flue installations MUST be fitted with ESCONDK." on page 21.
If a horizontal terminal is used cut in accordance with"CUTTING ~ ASPDFK, ASPKIT03, ESPIPE900 &
ESROOFCOWL FLUE PIPES" on page 19 and assemble and connect in accordance with "ASSEMBLING AN
ON-WALL TERMINAL ~ ESWTKIT, ESBEND & ESPIPE900" on page 20.
8. Move the heater into place and make the heater exhaust and combustion air hose connections in accordance
with the section "CONNECTING CONDENSATE DRAIN KIT TO HEATER" on page 23.
9.
Use ONLY the supplied silicone based 'O Ring' seal lubricant. DO NOT use petroleum based lubricants such
as petroleum jelly. The use of petroleum jelly, vaseline
deterioration of the 'O Ring' seals.
Air hose and heater exhaust connections at the heater MUST be made and checked in accordance
with these instructions. Improper connections may result in dangerous situations, for example, the
CAUTION
dispersion of combustion products in the space being heated.
10. Refere to the chapter "Heater Installation" in the "Rinnai Operation / Installation Manual" supplied with the heater
and complete the installation and commissioning of the heater in accordance with these.
Rinnai
FLUE COMPONENT ASSEMBLY
Min' required protrusion 50mm
22mm x 3
7mm x 2
5
!
The wall plate is then secured to the outer pipe of the flue protrusion using the
!
®
or similar petroleum based lubricants will cause rapid
13
6
Align the arrow
POWER FLUED FLAMEFIRE FIM