Daikin FTKS09SL216 Service Manual page 55

Table of Contents

Advertisement

(4) Start-up failure (following AP1 for outdoor unit control board)
Mainly detect:
●Whether the compressor wiring is connected correct?
●Is compressor broken?
●Is time for compressor stopping enough?
Fault diagnosis process:
52
Power on the unit
Is stop time of the compressor
longer than 3 minutes?
Y
Does startup fail?
Y
Are the wires for the compressor connected
correctly? Is connection sequence right?
Y
Replace the control panel AP1
N
If the fault is eliminated?
N
Replace the
compressor
End
Restart it up after
N
3 minutes
Connect the wires as
N
per the connection
diagram
Y
Service Manual
Installation and Maintenance

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents