Connections - Pepperl+Fuchs FIELDBUS Manual

Compact fieldbus power hub, generic interface
Table of Contents

Advertisement

Compact Fieldbus Power Hub,Generic Interface
Installation and Commissioning
Connecting the Host
The motherboard is connected to the host system via designated screw terminals.
_
Tr un k
+
Host +
-
Host -
S
Shield
Grounding
The motherboard is connected to the earth via designated screws.
If needed, an optional grounding rail can be applied.
The torque required for tightening the grounding screws: 1.5 Nm
3.3.1

Connections

1
Primary bulk power connection with mounted connector cover for Ex ic installations
2
Host connection
3
Secondary connection with mounted connector cover for Ex ic installations
4
Common alarm voltage-free contact with final motherboard link (The alarm contact has
to be looped at the last motherboard)
5
Diagnostic bus connection
6
Connections for fieldbus trunk
7
Diagnostic link cable ACC-MB-HDC
20
S
1
2
7
3
4
5
6

Advertisement