Fieldbus Surge Protector Safety Safety Validity The chapter “Safety” is valid as instruction manual. Specific processes and instructions in this instruction manual require special provisions to guarantee the safety of the operating personnel. Symbols Used This document contains symbols for the identification of warning messages and of informative messages.
Due to constant revisions, documentation is subject to permanent change. Please refer only to the most up-to-date version, which can be found under www.pepperl-fuchs.com. Marking The Surge Protectors are marked with: Pepperl+Fuchs Group Lilienthalstraße 200, 68307 Mannheim, Germany TPH-LBF-IA1.36.DE.0 TPH-LBF-IA1.36.DE.1...
Intended Use The TPH-LBF*, TCP-LBF* and SCP-LBF* series of Surge Protectors are intended to be used in conjunction with Pepperl+Fuchs Fieldbus Power Hubs and Device Couplers, to protect them from damage caused by surge voltages or secondary lightning strikes.The Surge Protectors are specifically designed for IEC 61158-2 FOUNDATION fieldbus and PROFIBUS PA fieldbus communication systems.
Fieldbus Surge Protector Safety Instructions for Zone 1 Due to the presence of gas discharge tubes, the surge protective devices do not meet the dielectric strength requirements according to IEC/EN 60079-11 between the intrinsically safe circuits and the parts that may be grounded. Instructions for Zone 21 Due to the presence of gas discharge tubes, the surge protective devices do not meet the dielectric strength requirements according to IEC/EN 60079-11 between the intrinsically...
Fieldbus Surge Protector Safety Delivery, Transport, and Storage Check the packaging and contents for damage. Check if you have received every item and if the items received are the ones you ordered. Keep the original packaging. Always store and transport the device in the original packaging. Always store the device in a clean and dry location.
The TPH-LBF*, TCP-LBF*, and SCP-LBF* series Surge Protectors consist of pluggable units, designed to fit directly into 3-pin terminals socket of Pepperl+Fuchs fieldbus components as Power Hubs, Segment Protectors and FieldBarriers, to protect trunk and spur connections of a fieldbus installation.
Page 11
Fieldbus Surge Protector Product Specifications The following table gives an overview about types and their specific usage in combinations with Pepperl+Fuchs fieldbus components: Type Description Shield connection Predictive Hazardous area diagnosis TCP-LBF- Surge Protector for Indirectly grounded No diagnostics Entity, FISCO, IA1.36.IE.0...
Page 12
‘end of effective life’. At this point, the diagnostic electronics generates an alarm that the Pepperl+Fuchs Advanced Diagnostics infrastructure receives, whereon this alarm will be transmitted to the system’s maintenance or operator terminal, containing Pepperl+Fuchs Advanced Diagnostic Manager software.
Fieldbus Surge Protector Product Specifications Component Identity To protect Pepperl+Fuchs Fieldbus Power Hubs and fieldbus couplers from damage caused by surge voltages or secondary lightning strikes, you can install the TPH-LBF*, TCP-LBF*, or SCP-LBF* Surge Protectors series. The TCP-LBF* Surge Protectors protect the trunk connection and the SCP-LBF* Surge Protectors protect the spur connection of fieldbus couplers.
Page 14
Fieldbus Surge Protector Product Specifications 2.2.1 Protection of Segment Protector Figure 2.1 Grounding rail ACC-LBF-EB.6 Separation wall ACC-LBF-SW Terminator M-FT* T-connector Surge Protector TCP-LBF-IA1.36.IE* Segment Protector R2-SP-* or R3-SP-* Surge Protector SCP-LBF-IA1.36.IE* Spur connector The Surge Protector TCP-LBF-IA1.36.IE* mounts on the trunk connection of the Segment Protector.
Page 15
Grounding rail ACC-LBF-EB.8 suitable for MBHC-FB-8R* Motherboards Power Hub Motherboard MBHD-FB1-4R* Power Hub Motherboard MBHC-FB-8R* Surge Protector TPH-LBF-IA1.36.IE* Trunk connector The Surge Protector TPH-LBF-IA1.36.IE* mounts on the trunk connection of the Power Hub Motherboard. Use 1 Surge Protector for each trunk connection. See chapter 3.2.3...
Product Specifications Technical Data 2.3.1 TPH-LBF-IA1.36.DE.* Fieldbus interface Self current consumption max. 6 mA (for version TPH-LBF-IA1.36.DE.1) , max. 0 mA (for version TPH-LBF-IA1.36.DE.0) Indicators/operating means LED ERR green flashing: status OK , red flashing: maintenance required , (for version TPH-LBF-IA1.36.DE.1)
Page 17
Fieldbus Surge Protector Product Specifications 2.3.2 TCP-LBF-IA1.36.IE* Fieldbus interface Self current consumption max. 6 mA (for version TCP-LBF-IA1.36.IE.1) , max. 0 mA (for version TCP-LBF-IA1.36.IE.0) Indicators/operating means LED ERR green flashing: status OK , red flashing: maintenance required , (for version TCP-LBF-IA1.36.IE.1) Electrical specifications Rated voltage 36 V...
Page 18
Fieldbus Surge Protector Product Specifications 2.3.3 SCP-LBF.IA1.36.IE.* Fieldbus interface Self current consumption max. 6 mA (for version SCP-LBF-IA1.36.IE.1) , max. 0 mA (for version SCP-LBF-IA1.36.IE.0) Indicators/operating means LED ERR green flashing: status OK , red flashing: maintenance required (for version SCP-LBF-IA1.36.IE.1) Electrical specifications Rated voltage 36 V...
Fieldbus Surge Protector Installation Installation Installation of Surge Protector Prior to mounting, installation, and commissioning of the device you should make yourself familiar with the device and carefully read the instruction manual. Observe the EC-type-examination certificate. It is especially important to maintain any "special conditions for safe use"...
Page 22
Fieldbus Surge Protector Installation 3.2.1.1 Mounting the Surge Protector Mounting Remove the T-connector and Terminator from the trunk connection (1). Plug the Surge Protector in the trunk connection and fix the Surge Protector with the 2 screws on the Segment Protector (2). Plug the T-connector in the trunk connection of the Surge Protector and fix the T-connector with the 2 screws (3).
Page 23
Fieldbus Surge Protector Installation Connect the grounding rail to the grounding terminal of the housing (5). The grounding terminal should be connected to an equal potential bonding system using a minimum cross core section of 4 mm The shield connection of the trunk is internally indirectly connected to the grounding terminal through a gas discharge tube.
Page 24
Fieldbus Surge Protector Installation Connect the ground cable to a cable lug Position the cable lug (3) over the grounding terminal so that the cable points downwards. Screw the cable lug (3) to the grounding terminal (4) using 2 toothed lock washers (2). Tighten the screw with a torque of 1.5 Nm (1).
Page 25
Fieldbus Surge Protector Installation 3.2.2 Surge Protector SCP-LBF-IA1.36.IE* for Spur Connection SCP-LBF-IA1.36.IE* Surge Protectors in combination with the fieldbus couplers R2-SP*, R3-SP*, R4D0-FB*. The Surge Protector comes without a spur connector. The spur connector has to be taken from the fieldbus coupler the Surge Protector will be used with. 3.2.2.1 Mounting the Surge Protector for Spur Connections Mounting...
Page 26
Fieldbus Surge Protector Installation Plug the spur connector into the Surge Protector and fix the spur connector with 2 screws (3). Mount the grounding rail at the bottom of the Surge Protector (4). Note that you can connect multiple Surge Protectors via one single grounding rail. Connect the grounding rail to the grounding terminal of the housing (5).
Page 27
3.2.2.2 Grounding rail ACC-LBF-EB.6 For attaching Surge Protectors to the spur connections of Pepperl+Fuchs fieldbus couplers R2-SP*, R3-SP*, and F4D0-FB-IA*, the optional grounding rail ACC-LBF-EB.6 is used to provide a common earth point and mechanical support for up to 6 SCP-LBF-1.36* modules.
Page 28
Surge Protector TPH-LBF-IA1.36.DE* Trunk Connection for Power Hub TPH-LBF-IA1.36.DE* Surge Protectors in combination with Power Hub Motherboards. Warning! WARNING! The TPH-LBF-IA1.36.DE.1 Surge Protector must not be used in combination with the DART Power Hub Backplane MBHD-FB-D*! 3.2.3.1 Mounting the Surge Protector Mounting on Motherboards (*-8R) Remove the trunk connector from the trunk connection (1).
Page 29
Fieldbus Surge Protector Installation Mount the grounding rail at the bottom of the Surge Protector (4). Note that you can connect multiple Surge Protectors via one single grounding rail. Connect the grounding rail to the grounding terminal of the housing (5). Figure 3.1 Mounting on 8-channel motherboards (*-8R) Mounting on Rotated Motherboards (*-8R.R)
Page 30
Fieldbus Surge Protector Installation Plug the trunk connector into the Surge Protector and fix the trunk connector with 2 screws (3). Mount the grounding rail in 2 parts on the motherboard. Separate the grounding rail and rotate one of them before mounting, see figure. Figure 3.2 Preparation of the grounding rail mounting Mount the grounding rail at the bottom of the Surge Protector (4).
Page 31
Mounting on rotated 8-channel motherboards (*-8R.R) 3.2.3.2 Grounding Rail ACC-LBF-EB.8 For attaching Surge Protectors to the trunk connections of the Pepperl+Fuchs Power Hub MBHD-FB1*, the optional grounding rail ACC-LBF-EB.8 is used to provide a common earth point and mechanical support for the TPH-LBF-1.36* modules.
Page 32
Fieldbus Surge Protector Installation 3.2.3.4 Connect the Grounding Rail to the Grounding Terminal of the Housing 1. Position the cable lug (3) over the grounding terminal (4) so that the cable points downwards. 2. Screw the cable lug to the grounding terminal (4) using 2 toothed lock washers (2). 3.
TPH-LBF-IA1.36.DE.1 Surge Protector for Power Hub trunk connection, diagnostics included, shield directly grounded. ACC-LBF-SW.3 Separation wall for TPH-LBF-IA1.36* in Ex ic application. Package of 3 pieces. TCP-LBF-IA1. 36.IE.1 Surge Protector for fieldbus coupler trunk connection, diagnostics included, shield grounded through GDT.